<strong>Configuring</strong> PROFINET IO Devices<br />

4.2 Steps For <strong>Configuring</strong> a PROFInet IO System<br />

4.2.1 Overview: From Configuration To Cyclical Data Exchange<br />

The following sections describe the basic steps required to place a PROFINET IO<br />

system in operation. It tells you how to configure PROFINET components, assign<br />

addresses <strong>and</strong> how the system starts.<br />

<strong>Configuring</strong> an IO system in HW Config<br />

Assign addresses<br />

Startup<br />

1. Assign parameters to an IO controller (i.e. CPU 317-2 PN/DP) in HW Config.<br />

While assigning the interface parameters, assign an Ethernet subnet <strong>and</strong> an IP<br />

address.<br />

2. Arrange all required IO devices in the IO system ("railroad track").<br />

3. For each IO device: check the device name, <strong>and</strong>, if necessary, change it <strong>and</strong><br />

set its parameters.<br />

1. Each IO device must have the configured device name assigned to it.<br />

2. Download the hardware configuration while the CPU is in STOP mode.<br />

The configured IP address is automatically assigned to the PN interface (e.g. a<br />

CPU) when the hardware configuration is downloaded.<br />

At startup, the CPU transfers the downloaded configuration via the PN interface to<br />

the IO devices. As with PROFIBUS DP, the "'Finished' message by modules" <strong>and</strong><br />

"Transfer of parameters to modules" monitoring times that are assigned as<br />

parameters apply here as well.<br />

At startup, the CPU can identify the IO devices by their device names <strong>and</strong><br />

automatically transfer the associated IP addresses.<br />

After the addresses <strong>and</strong> parameters have been successfully transferred within the<br />

monitoring times, the PROFINET devices start their cyclical data exchange.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />