24.10.2013 Views

Configuring Hardware and Communication Connections STEP 7.pdf

Configuring Hardware and Communication Connections STEP 7.pdf

Configuring Hardware and Communication Connections STEP 7.pdf

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Networking Stations<br />

Which Modules or Stations Must Be Loaded After a Change to a Network<br />

Configuration?<br />

If you change a configuration as follows ... ... you have to reload<br />

Delete or add a network connection to a station (station All network gateways<br />

equals network gateway)<br />

Modify an interface address on the subnet (station equals Network gateways on the same subnet<br />

network gateway) or<br />

plug a module with its own MPI address into an S7-300<br />

station in such a way that the MPI address of a network<br />

gateway (next module inserted) is changed<br />

Add or delete a network gateway All network gateways<br />

Insert a module with a network connection in another slot All modules for this station<br />

(station equals network gateway)<br />

Add a subnet -<br />

Delete a subnet (where network gateways are configured All network gateways<br />

on this subnet)<br />

Change a subnet ID If any network gateways are connected to<br />

this subnet: All network gateways<br />

S7 Subnet ID for an Online Connection via Network Gateways<br />

If the network configuration together with all the routing information was<br />

downloaded to the affected stations, you must also specify an S7 subnet ID to<br />

access the remote station.<br />

The S7 subnet ID that is requested by <strong>STEP</strong> 7 using dialog boxes is formed from<br />

two numbers:<br />

• A number for the project<br />

• A number for the subnet<br />

Both numbers can be determined via the properties dialog box of the subnet with<br />

an existing network configuration. If you want to go online with a programming<br />

device without a consistent project, you must know the subnet ID. The subnet ID is<br />

printed out with the network configuration.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

11-32 A5E00706939-01

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!