<strong>Configuring</strong> the Distributed I/O (DP)<br />

How to find nodes in the topology view<br />

In larger configurations you can locate a required node via the menu comm<strong>and</strong><br />

Options > Go To. The next dialog box "Go To" displays all nodes of the<br />

PROFIBUS network:<br />

1. Select the required node (e.g. a DP slave)<br />

2. Click on the "Node" button to display the node in the center of the window.<br />

Click on the "Diagnostic repeater" button to display the assigned in the center<br />

of the window.<br />

Display of the topology in tables<br />

If you prefer to display the topology in a table rather than graphically, call menu<br />

comm<strong>and</strong> View > Table > Topology.<br />

Preparing line diagnostics<br />

Use the same procedure as in HW Config or under NetPro. In the topology display,<br />

call menu comm<strong>and</strong> PLC > Prepare Line Diagnostics.<br />

Calling the module status<br />

Use the same procedure as in HW Config or under NetPro. In the topology display,<br />

call menu comm<strong>and</strong> PLC > Module Status.<br />

How to save <strong>and</strong> open topology data<br />

Select the menu comm<strong>and</strong> File > Save or File > Save As to save the current<br />

display. This function allows to easily save the data you have acquired online for<br />

the purpose of later diagnostics <strong>and</strong> error evaluation.<br />

How to export topology data<br />

You can use the following view to export topology data:<br />

• The "Table" view (after calling menu comm<strong>and</strong> View > Table)<br />

• The "Statistics" dialog box (after calling menu comm<strong>and</strong> PLC > Statistics)<br />

• The "Diagnostics buffer" dialog box (after calling menu comm<strong>and</strong> PLC ><br />

Diagnostics Buffer)<br />

The CSV (ASCII) export format can be read <strong>and</strong> edited with other applications.<br />

The topology display can no longer read exported data.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />