<strong>Configuring</strong> PROFINET IO Devices<br />

Reading <strong>and</strong> setting the update time globally from a central location<br />

Tip<br />

To open the dialog to read <strong>and</strong> change the update time, proceed as follows:<br />

1. Double-click the IO system (the "railroad track").<br />

2. Select the "Update Time" tab.<br />

- If, in addition to PROFINET IO, other cyclical services (i.e. from<br />

Component-based Automation, CBA) have to be taken into consideration:<br />

Go to the "<strong>Communication</strong> Component (PROFINET IO)" field <strong>and</strong> select a<br />

percentage that should be reserved for PROFINET IO.<br />

If at least one IO device is configured, then the default setting is 100%.<br />

If no IO device is configured, then the default setting is 0%.<br />

- Select the desired option for setting the update time: for the entire IO<br />

system or for a specific device.<br />

3. If you like, you can increase the update time (for the entire IO system or for a<br />

specific IO device).<br />

Regardless of the option that you select: the dialog always shows the calculated or<br />

already configured update times. This applies to a setting for the entire IO system<br />

or a setting for a specific IO device.<br />

Reading <strong>and</strong> setting the update time at the IO device<br />

To open the dialog to read <strong>and</strong> change the update time for specific IO device,<br />

proceed as follows:<br />

1. Double-click the IO device.<br />

2. Select the "IO Cycle" tab.<br />

3. Check the current setting for the update time. If necessary, change it <strong>and</strong> then<br />

confirm the settings with "OK".<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 4-9