<strong>Configuring</strong> Central Racks<br />

2.4 Exp<strong>and</strong>ing the Central Rack with Expansion Racks<br />

<strong>Configuring</strong> Expansion Racks in SIMATIC 300<br />

For SIMATIC 300 stations, only "Rails" are available as central racks <strong>and</strong> as<br />

expansion racks; this means you can position as many rails (max. 4) as there are<br />

in the actual configuration.<br />

Expansion racks are linked in <strong>STEP</strong> 7 by inserting the appropriate interface module<br />

in slot 3 of every rack.<br />

• To exp<strong>and</strong> the configuration by one rack:<br />

racks 0 <strong>and</strong> 1: IM 365<br />

• To exp<strong>and</strong> the configuration by up to three racks:<br />

rack 0: IM 360; racks 1 to 3: IM 361<br />

<strong>Configuring</strong> Expansion Racks in SIMATIC 400<br />

In SIMATIC 400, the possibilities for expansion are more complex owing to the<br />

different racks <strong>and</strong> interface modules.<br />

All expansion racks that are connected to an interface of the send IM on the central<br />

rack form a cascade.<br />

In the following figure, three expansion racks are connected to each interface of the<br />

send IM.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 2-19