Networking Stations<br />

11.6.8 Checking the Consistency of the Network<br />

Before you save, you should check the network configuration for consistency. The<br />

following are reported, for example:<br />

• Nodes that are not connected to a subnet<br />

(exception: non-networked MPI nodes)<br />

• Subnets that have only one node<br />

• Inconsistent connections<br />

Requirement<br />

NetPro must be open.<br />

Procedure<br />

• Select the menu comm<strong>and</strong> Network > Check Consistency.<br />

Result: A window "Outputs for Consistency Check" with hints for configuring<br />

conflict-free networks <strong>and</strong> connections is displayed.<br />

Inconsistent stations are color-coded in red.<br />

Tip<br />

You can select the window containing the results of the last consistency check at<br />

any time using the menu comm<strong>and</strong> View > Errors <strong>and</strong> Warnings.<br />

Alternative Procedure<br />

1. Select the menu comm<strong>and</strong> Network > Save <strong>and</strong> Compile.<br />

2. In the dialog box, select the option "Check <strong>and</strong> compile all."<br />

The "Outputs for Consistency Check" Window<br />

Messages <strong>and</strong> warnings are entered in this window if the consistency check found<br />

incorrect project planning/configuration (can refer to the hardware configuration,<br />

network or connection planning). A consistency check is carried out during the<br />

following actions:<br />

• Menu comm<strong>and</strong> Network > Check Consistency<br />

• Menu comm<strong>and</strong> Network > Network > Check Cross-Project Consistency<br />

• Menu comm<strong>and</strong> Network > Save <strong>and</strong> Compile<br />

• Download to PLC (consistency check for the stations or connections to which<br />

downloading is to be carried out)<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />