<strong>Configuring</strong> <strong>Connections</strong><br />

"Address Details" Dialog Box for S7 <strong>Connections</strong> to a Partner in a different<br />

Project<br />

In the dialog boxes for the connection properties (Properties S7 Connection dialog<br />

box <strong>and</strong> Address Details dialog box) of an unspecified partner, you have to enter or<br />

select the address (of the interface), the end point of the connection (rack/slot), <strong>and</strong><br />

the connection resources of each "Other Side" (that is, of the connection partner).<br />

Example: The following configuration is a prerequisite:<br />

The stations are in different projects. The CPU as connection end point is in the<br />

central controller (rack 0) slot 4 in both projects. Both stations are networked by<br />

means of the PROFIBUS interface of a CP.<br />

The following table shows which supplementary information is required for the<br />

configuration shown in order to enable a connection setup in operation.<br />

Information in Dialog Boxes on<br />

the Unspecified Connection<br />

Partner...<br />

... for Project 1 ...for Project 2 Comments<br />

Active connection setup Yes No Dialog box: Properties S7<br />

Connection<br />

Address (interface) Local/Partner Local: 2 Local: 3 Dialog box: Properties S7<br />

Partner: 3 Partner: 2 Connection, under Connection<br />

Path; the addresses have to<br />

match "crosswise".<br />

Rack/slot Local: 0/4 Local: 0/4 Dialog box: Address Details"<br />

Partner: 0/4 Partner: 0/4<br />

Connection resource (hex) Local: 10 Local: 11 Dialog box: Address Details;<br />

(Local/Partner)<br />

Partner: 11 Partner: 10 connection resources cannot be<br />

assigned twice <strong>and</strong> must match<br />

"crosswise".<br />

TSAP (Transport Service Access<br />

Point)<br />

Is displayed<br />

(cannot be<br />

changed)<br />

Is displayed<br />

(cannot be<br />

changed)<br />

Dialog box: Address Details;<br />

for station-internal addressing of<br />

the interface, by means of the<br />

connection "Running" (is made<br />

up of the address details)<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

12-42 A5E00706939-01