<strong>Configuring</strong> the Distributed I/O (DP)<br />

<strong>Configuring</strong> the CP 342-5 as a DP Slave<br />

Procedure<br />

The CP 342-5 can be configured for operation as a DP slave. The station in which<br />

the CP was configured is then an "intelligent slave."<br />

1. Configure a station with the CP 342-5 DP as DP slave.<br />

(Select the option "DP slave" in the "Operating Mode" tab of the CP.)<br />

2. Configure a DP master (CPU with integrated PROFIBUS-DP interface or CP<br />

with PROFIBUS-DP interface) in another station.<br />

3. Drag the CP 342-5 from the "<strong>Hardware</strong> Catalog" window (Configured<br />

Stations folder) <strong>and</strong> drop it onto the symbol for the DP master system<br />

( ).<br />

A dialog box appears in which you can select configured intelligent DP slaves.<br />

4. Confirm your selection with "OK."<br />

5. Configure the DP IDs <strong>and</strong> addresses for the input <strong>and</strong> output areas in the<br />

displayed configuration table for the DP slave. To do this, drag <strong>and</strong> drop the<br />

"Universal Module" from the "<strong>Hardware</strong> Catalog" window (Configured<br />

Stations folder) into the configuration table (lower half of the station window)<br />

<strong>and</strong> then double-click the corresponding row.<br />

Note<br />

Data exchange between a "preprocessing CPU" <strong>and</strong> a CP 342-5 DP within the DP<br />

slave is described in the SIMATIC NCM documentation.<br />

<strong>Configuring</strong> the CPU 31X-2 DP or CPU 41X-..DP as a DP Slave<br />

CPUs with integrated DP interface (such as CPU 315-2 DP) can be configured for<br />

operation as a DP slave. The station is which the CPU was configured is then the<br />

"intelligent slave."<br />

The procedure for a CPU 315-2 DP is described below. The procedure is always<br />

the same, save for the selection of the CPU type (also refer to Example for the<br />

Configuration of an S7-400 as I-Slave).<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />