<strong>Configuring</strong> <strong>Connections</strong><br />

Case 2: Configuration with non-redundant H-Station (local) <strong>and</strong> redundant H-<br />

Station (remote)<br />

In this case, there is a difference whether the redundant partner station is fitted<br />

with a total of two or four CPs.<br />

If the partner station is fitted with a total of two CPs, then one connection resource<br />

is reserved on the local H-CPU <strong>and</strong> two connection resources are reserved on the<br />

local CP.<br />

If the partner station is fitted with a total of four CPs <strong>and</strong> the "Enable max. CP<br />

redundancy" option was selected, then a total of four connection paths is possible.<br />

Even so, one connection resource is reserved the local H-CPU, <strong>and</strong> two<br />

connection resources are reserved for the local CP. The reason for this is that a<br />

maximum of two partial connections can be active.<br />

(1) Partial connection<br />

(2) Fault-tolerant S7 connection<br />