<strong>Configuring</strong> PROFINET IO Devices<br />

Procedure<br />

1. In HW Config or in NetPro, select the PLC > Ethernet > Assign Device Name<br />

menu comm<strong>and</strong><br />

2. In the "Assign Device Name" dialog box, go to the "Device Name" field <strong>and</strong><br />

select a device. Then, in the "Available Devices" field, select the device to<br />

receive the selected device name.<br />

3. To make the device easier to identify, click the "Flashing" button to cause a<br />

display LED in the selected device to flash.<br />

4. Click the "Assign Name" button.<br />

5. Repeat steps 2 through 4 until you have assigned a name to all the devices.<br />

Starting the CPU<br />

After the names are all assigned, you can put the CPU into RUN mode.<br />

At startup, the CPU distributes the configuration information to the IO devices <strong>and</strong><br />

then goes into cyclical operation.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

4-28 A5E00706939-01