17.4 Entering or Changing M-Data in HW Config<br />

Requirements<br />

Procedure<br />

• The module must support I&M data.<br />

• There is an online connection through PROFIBUS to the module.<br />

To edit M data (such as the Plant ID), proceed as follows:<br />

1. Double-click the module. In the property sheet that is displayed, select the<br />

"Identification" tab.<br />

2. Enter the M data <strong>and</strong> then confirm your entries with "OK".<br />

3. Select the PLC > Download Module Identification menu comm<strong>and</strong>.<br />

4. In the "Download Module Identification" dialog box, compare the offline data in<br />

the <strong>STEP</strong> 7 database with the data at the module ("ONLINE").<br />

5. To overwrite the online data with the offline data, select the "Include" check<br />

box.<br />

6. Confirm your settings with "OK".<br />

The M data will be transferred to the module<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

17-6 A5E00706939-01