<strong>Configuring</strong> the Distributed I/O (DP)<br />

Assigning Parameters<br />

System Requirements<br />

<strong>STEP</strong> 7 as of version 5.1, SP 2, Hotfix 1 <strong>and</strong> SIMATIC PDM optional package as of<br />

version 5.1, SP 2 or PCS7 as of version 5.2.<br />

To be able to work with PDM online, you require a PROFIBUS DP interface e.g.<br />

CP5611 (6GK1 561-1AA00). The CP has to be set at the PROFIBUS DP interface<br />

(in the SIMATIC Manager via: Extras > Setting the PG/PC Interface).<br />

Assigning Parameters to the Electronic Module<br />

1. In HW Config, double-click the first electronic module in the configuration table.<br />

2. Select "Specialist" in the subsequent dialog box as user <strong>and</strong> confirm with "OK";<br />

you can assign parameters in this mode.<br />

3. SIMATIC PDM is started with the current parameters <strong>and</strong> identification data of<br />

the module.<br />

4. Set the parameters of the electronic module using the SIMATIC PDM, save the<br />

parameters (via File > Save menu comm<strong>and</strong>) <strong>and</strong> load them via the Device ><br />

Load Into Device menu comm<strong>and</strong> into the electronic module; exit SIMATIC<br />

PDM.<br />

5. Double-click the next electronic module in the configuration table <strong>and</strong> repeat<br />

steps 2 <strong>and</strong> 3 until you have configured all electronic modules.<br />

Assigning Parameters to the Interface Module.<br />

1. In HW Config, double-click on DP slave "IM 151-2" (in the upper part of the<br />

station window). Select "Specialist" in the subsequent window; SIMATIC PDM<br />

is started.<br />

2. Set the parameters of the IM 151-2 interface module, save the parameters (via<br />

File > Save menu comm<strong>and</strong>) <strong>and</strong> download the parameters into the interface<br />

module via the Device > Load Into Device menu comm<strong>and</strong>; exit SIMATIC<br />

PDM.<br />

Assigning Parameters to all ET 200iS modules.<br />

1. In HW Config, double-click on DP slave "IM 151-2" (in the upper part of the<br />

station window). Select "Specialist" in the subsequent window; SIMATIC PDM<br />

is started <strong>and</strong> all ET 200iS modules are loaded.<br />

2. Download all module parameters (via the File > Load into Programming<br />

Device/PC menu comm<strong>and</strong>).<br />

3. Assign parameters to all necessary modules. You can navigate to all ET 200iS<br />

modules from the left panel of SIMATIC PDM.<br />

4. Save the changes (via File > Save menu comm<strong>and</strong>) for the file to be updated.<br />

5. Load all parameters into the modules (via Device > Load into Device menu<br />

comm<strong>and</strong>); exit SIMATIC PDM.<br />

You can also parameterize ET 200iS only with SIMATIC PDM (For more<br />

information, see the SIMATIC PDM online Help.)<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />