3.6 Other DP Slave Configurations<br />

3.6.1 ET 200L <strong>and</strong> DP/AS-i Link<br />

3.6.2 ET 200S<br />

Introduction<br />

Note<br />

<strong>Configuring</strong> the Distributed I/O (DP)<br />

When configuring the DP slaves ET 200L <strong>and</strong> DP/AS-i Link (distributed<br />

I/O/actuator-sensor interface), the following applies:<br />

• ET 200L can be exp<strong>and</strong>ed using Smart Connect (SC) a channel at a time<br />

• DP/AS-i Link is configured with actuator-sensor interface slaves; see below.<br />

When placing a DP/AS-i Link, a configuration table is displayed automatically in<br />

which you can place the actuator-sensor interface slaves from the "<strong>Hardware</strong><br />

Catalog" window.<br />

DP slaves <strong>and</strong> IO devices of the ET 200S family are configured like other modular<br />

DP slaves <strong>and</strong> IO devices.<br />

Special feature: Digital electronic modules with an address space of 2 bits initially<br />

occupy 1 byte when they are inserted in the configuration table (Details view).<br />

However, the occupied address space can be compressed after configuration by<br />

means of the Pack Addresses button.<br />

Example:<br />

Before Packing<br />

Addresses<br />

After Packing<br />

Addresses<br />

Module I Address I Address<br />

DI_1_Module 10.0 to 10.1 10.0 to 10.1<br />

DI_2_Module 11.0 to 11.1 10.2 to 10.3<br />

Addresses cannot be packed in the GSD-based variant of the ET 200S IO device.<br />

In the HW catalog, use the variant that does not have a reference to a GSD file<br />

(*.XML) in its info text.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 3-17