<strong>Configuring</strong> Global Data <strong>Communication</strong><br />

13.5.6 Entering Scan Rates<br />

Introduction<br />

Global data exchange occurs as follows:<br />

• The sender CPU sends the global data at the end of a cycle.<br />

• The receiver CPU reads the data at the start of a cycle.<br />

With the aid of the scan rate, you can determine after how many cycles the data<br />

will be sent or received.<br />

Procedure<br />

1. Compile the global data table if it is not already in phase 1 (you can view this<br />

information in the status bar at the bottom edge of the screen).<br />

2. If no scan rates are displayed in the GD table, select the menu comm<strong>and</strong><br />

View > Scan Rates.<br />

3. Enter the required scan rates. You can enter data only in the columns in which<br />

the GD packet in question has entries.<br />

Note: When you view status rows <strong>and</strong>/or scan rate rows, you can edit these<br />

rows only.<br />

4. Compile the global data table again (phase 2).<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />