2. Necessary previous knowledge<br />

2.2 System structure<br />

The nurse call system uses a bus system which comprises a group bus OSYnet<br />

and a room bus RAN. The group bus OSYnet links the individual rooms and potential<br />

interfaces in the ward. The room bus RAN links the equipment and<br />

<strong>de</strong>vices in the rooms themselves.<br />

The respective room terminal controls the room bus RAN and forms the<br />

connection between room bus RAN and group bus OSYnet: ComTerminal <strong>Flamenco</strong>,<br />

RoomTerminal <strong>Flamenco</strong>, ControlTerminal <strong>Flamenco</strong>, ControlTerminal<br />

with doorplate <strong>Flamenco</strong>.<br />

System control is realised in the OSY-ControlCenter which controls the data<br />

flow as well as all speech communication.<br />

If the OSY-ControlCenter should fail or break down, <strong>de</strong>centralised OSYnet-<br />

SafetyControllers can takeover the control of the basic nurse call functions.<br />

These controllers are fitted to ward's OSYnet group bus.<br />

Decentralised power supply units provi<strong>de</strong> the electric power for the system.<br />

Number of units and their location <strong>de</strong>pend on the specific <strong>de</strong>mand for electric<br />

power. Power for the OSY-ControlCenter is also provi<strong>de</strong>d via an external power<br />

supply unit.<br />

Group 4<br />

Group 3<br />

OSYnet<br />

Group 2<br />

RAN<br />

RAN<br />

Room 1 Room 2<br />

OSYnet<br />

Group 1<br />

PS<br />

DECT<br />

HIS<br />

...<br />

RAN<br />

RAN<br />

OSY-ControlCenter Room 1 Room 2<br />

Fig. 2:<br />

System structure<br />

8<br />

<strong>Flamenco</strong> - <strong>Technical</strong> <strong>Manual</strong>, 04/13 (Rev. <strong>6.0</strong>), 00 8812 60