12. Functional checks<br />

12.1.2 Check light call function for each room<br />

12.1.2.1 Check each room<br />

The following test is performed to check all call <strong>de</strong>vices in the room:<br />

Start<br />

yes<br />

LED for<br />

call button (red)<br />

weak light.<br />

no<br />

Correct the fault.<br />

Press call button<br />

(red).<br />

LED for call button<br />

(red) bright.<br />

Room lamp:<br />

Red flashing.<br />

Activate<br />

presence 1<br />

(green).<br />

LED in presence<br />

button (green).<br />

is on<br />

Room lamp:<br />

Red is on.<br />

Green is on.<br />

Deactivate<br />

presence 1<br />

(green).<br />

LED for call button<br />

(red)<br />

weak light.<br />

LED in presence<br />

button (green)<br />

is off.<br />

Room lamp:<br />

Lights are off.<br />

Press call button<br />

(red).<br />

LED for call button<br />

(red) bright.<br />

Room lamp:<br />

Red flashing.<br />

Activate<br />

presence 2<br />

(yellow).<br />

LED in presence<br />

button (yellow)<br />

is on.<br />

Room lamp:<br />

Red is on.<br />

Yellow is on.<br />

Deactivate<br />

presence 2<br />

(yellow).<br />

LED for call button<br />

(red) weak light<br />

LED in<br />

presence button<br />

(yellow) is off.<br />

Room lamp:<br />

Lights are off.<br />