Power supply unit UPS 60, Or<strong>de</strong>r No. 77 3400 10<br />
8. Spare parts<br />
Spare part<br />
Or<strong>de</strong>r No.<br />
Mains fuse, front plate (5 x 20) T 5.0 A 00 0130 41<br />
Output fuse, bottom 15 A FKS 00 0132 02<br />
Clamp for mains connection, 3-pole 00 0211 40<br />
Clamp for 24 V connection, 4-pole 00 0211 41<br />
Clamp for control and indicator outputs, 7-pole 00 0211 39<br />
Clamp for battery connection, 2 pole 00 0211 20<br />
Bridging contact EB 2 – 5 for control clamps "x“ and "y“ 00 0223 56<br />
9. <strong>Technical</strong> data<br />
Power supply unit UPS 60 Or<strong>de</strong>r No. 77 3400 10<br />
Input<br />
Nominal input voltage<br />
115 – 230 V AC<br />
Input voltage range<br />
90 – 264 V AC<br />
Input frequency<br />
47 – 63 Hz<br />
Input current<br />
5.5 A at 115 V AC / 3 A at 230 V AC<br />
Start-up current surge<br />
22 A at 115 V AC / 44 A at 230 V AC, typical<br />
Power factor<br />
0.95 at 230 V AC / 0.98 at 115 V AC for full load<br />
Efficiency<br />
88%, typical<br />
Output<br />
Nominal output current<br />
12.5 A DC<br />
Output voltage 24 V DC +/- 2%<br />
Output voltage in battery mo<strong>de</strong><br />
26.5 – 19.5 V DC, typical<br />
Calculated output power<br />
288 W<br />
Rippling of nominal output current<br />
< 100 mV eff<br />
Battery capacity to be connected<br />
24 Ah<br />
Charge current<br />
3.0 A, typical<br />
Bridging time at nominal current<br />
approx. 1 hour<br />
Overload protection<br />
< 14 A<br />
Overvoltage protection, power supply unit<br />
26.7 – 32.4 V DC<br />
Overtemperature protection<br />
75 °C +/- 5°C (power dio<strong>de</strong>)<br />
output voltage switched off, automatic re-engaging<br />
Battery voltage thresholds<br />
Switching threshold for UPS mo<strong>de</strong><br />
U a < 22.5 V, typical<br />
Switching threshold for warning before battery<br />
21.5 V, typical<br />
shut-down<br />
Switching threshold for total discharge<br />
19.5 V, typical<br />
protection<br />
EMC CE-certified EN 55022 Class B; ENV 50204<br />
EN 61000-3-2, -3; EN 61000-4-2, -3, -4, -5, -6, -8, -11<br />
Safety EN 60950<br />
Output<br />
Safety low voltage, SELV<br />
Test voltage PRI – SEC<br />
3 kV<br />
Protection class<br />
I<br />
Ingress Protection IP 20<br />
Fuses<br />
Charging fuse, internal (5 x 20)<br />
T 4.0 A<br />
Mains fusing, front plate (5 x 20)<br />
T 5.0 A<br />
Output fusing, bottom of unit<br />
15 A FKS<br />
General<br />
Cooling<br />
convection, free air flow<br />
Permissible ambient temperature 0 ... +50 °C<br />
Storage temperature -25 ... + 60 °C<br />
MTBF<br />
100,000 hours<br />
Weight<br />
approx. 4 kg<br />
Dimensions (HxWxD)<br />
244 x 325 x 178 mm<br />
Mounting<br />
Wall mounting<br />
Connecting clamps<br />
Screw / cage clamp plug-in connections<br />
English - 6 © <strong>Tunstall</strong> GmbH, Orkotten 66, 48291 Telgte, Germany, www.tunstall.<strong>de</strong>, 00 8802 81, Rev. 3.0 (05/2012)<br />