Flamenco Technical Manual Revision 6.0 - Tunstall.de
Flamenco Technical Manual Revision 6.0 - Tunstall.de
Flamenco Technical Manual Revision 6.0 - Tunstall.de
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
6. Defining the mounting positions<br />
6.1.4 Switches<br />
150 mm<br />
Switches near the door<br />
91 mm<br />
1300 mm<br />
1-gang back box required for each switch.<br />
91 mm raster spacing is mandatory!<br />
300 mm<br />
Pull cord call switch in bathroom/WC<br />
(ceiling mounted)<br />
Or<strong>de</strong>r no.: 70 0115 00, 70 0115 01<br />
1-gang back box required.<br />
ÀÀ<br />
The pull cord grab may be not higher than 200 mm above the<br />
floor, so that people lying on the floor can reach the pull cord.<br />
ÀÀ ÀÀÀ<br />
ÀÀÀ<br />
300 mm<br />
Pull cord call switch in bathroom/WC<br />
(wall mounted)<br />
Or<strong>de</strong>r no.: 70 0115 00, 70 0115 01<br />
1-gang back box required.<br />
2250 mm<br />
Pull cord switches in shower stalls have to be installed at<br />
least 200 mm above the highest possible position of the<br />
showerhead. The pull cord grab may be not higher than<br />
200 mm above the floor, so that people lying on the floor can<br />
reach the pull cord.<br />
300 mm<br />
Pneumatic call switch<br />
Or<strong>de</strong>r no.: 70 0106 00, 70 0106 01<br />
1-gang back box required.<br />
2250 mm<br />
Back box solid wall, 1-gang: 17 0100 00<br />
Back box partition wall, 1-gang: 17 5100 00<br />
Note: The switch will be offset, i.e. the switch centre will be<br />
approx. 5 mm below the back box centre. In other words, install<br />
the back box 5 mm above the <strong>de</strong>sired switch position.<br />
Back box<br />
Switch<br />
5 mm<br />
<strong>Flamenco</strong> - <strong>Technical</strong> <strong>Manual</strong>, 04/13 (Rev. <strong>6.0</strong>), 00 8812 60<br />
47