11. Voltage surge protection<br />
11.1 SPD modules<br />
Functions<br />
SPD module base part<br />
BXT BAS<br />
Base part, for use as feed-through terminal for<br />
supporting SPD modules for speech and data<br />
lines. Modules pluggable without interruption, for<br />
4 single wires or 2 double wires. Width 12 mm<br />
(2/3 TE).<br />
‐ Mounting on 35 mm top hat rail acc. to 60715<br />
‐ Connection cross section finely stran<strong>de</strong>d:<br />
0.08 - 2.5 mm2<br />
‐ Earthing via 35 mm top hat rail acc. to<br />
EN 60715<br />
Or<strong>de</strong>r no.<br />
77 4900 00<br />
unit: mm<br />
SPD module for speech and data wires<br />
BXT ML4 BD HF 5<br />
Combined Lightning Current and Surge Arrester‐<br />
Module SPD class TYPE 1 / P1 tested acc. to<br />
EN 61643-21 and energy-coordinated acc. to<br />
IEC 61643-22 for protection of 2 pairs of IT<br />
sytems. For use with high data transmission<br />
rates due to its low self impedance.<br />
‐ For plugging into base part type BXT BAS.<br />
‐ SPD monitoring system: LifeCheck<br />
‐ Max. continuous operating DC voltage: <strong>6.0</strong> V<br />
‐ Nominal current for 45 °C: 1.0 A<br />
‐ D1 Total lightning impulse current (10/350):<br />
10 kA<br />
‐ Series impedance per wire: 1.0 Ohm<br />
‐ Shock test : EN 60068-2-27 (Ea test)<br />
‐ Examination of vibration performance<br />
(sinuoidal): EN 60068-2-6 (Fc test)<br />
‐ Test for vibration performance (coinci<strong>de</strong>ntal):<br />
EN 60068-2-64 (Fh test)<br />
77 4900 01<br />
unit: mm<br />
66<br />
<strong>Flamenco</strong> - <strong>Technical</strong> <strong>Manual</strong>, 04/13 (Rev. <strong>6.0</strong>), 00 8812 60