Power supply unit UPS, Or<strong>de</strong>r No. 77 3400 00<br />
6.1 Battery change<br />
Lead batteries contain harmful toxic substances. Observe general and local safety<br />
directives when during handling and transport. For disposal, comply with local directives.<br />
Pb<br />
Batteries bear the risk of excessive short-circuit currents. Never create any direct contact<br />
between the battery posts and or other conductive component parts. Therefore remove any<br />
wristband, watch, finger rings or other metal objects when working at the open power supply<br />
unit. Always use tools with standard isolating handles.<br />
Batteries may be replaced only by the same type of battery (2 x 12 V; 7 Ah). We recommend the use<br />
of the battery type BAT 24-7, <strong>Tunstall</strong> Or<strong>de</strong>r No. 00 0648 85. The use of other makes may create<br />
problems due to different connecting terminals or differing dimensions.<br />
1. Shut off mains supply to the power supply unit UPS !!!<br />
2. Release the 4 fastening screws for the left cover and remove the cover to the front.<br />
3. Confirm the position of the old battery and after its removal, install the new battery in the<br />
same manner.<br />
4. Make sure, the new battery is in the same position and check for the correct battery<br />
contacts. False connections may damage the power supply UPS !<br />
5. Check for the correct seating of the plastic cover for the batteries.<br />
6. Fix the battery position by securing it with the Velcro tape.<br />
7. Replace and close the housing.<br />
8. Perform a functional check of the power supply UPS!<br />
7. Storage<br />
If the power supply unit UPS will not be used for an exten<strong>de</strong>d period of time, the batteries must first<br />
be fully recharged to preclu<strong>de</strong> battery damage due to total discharging. (Refer to item 6 Battery<br />
service life).<br />
For the charging process, the power supply unit UPS shall be connected to the mains supply for at<br />
least 4 hours, and the UPS function shall be activated by placing the bridging contact between "x“ and<br />
"y“. After the charging process has been completed the power supply unit has to be disconnected from<br />
the mains supply and the battery fuse (un<strong>de</strong>r the left cover) has to be removed.<br />
8. Spare parts<br />
Spare part<br />
Or<strong>de</strong>r No.<br />
Rechargeable lead-gel battery, Type BAT 24-7 consisting of 2 batteries 00 0648 85<br />
Battery fuse, internal 20 A FKS 00 0132 03<br />
Mains fuse, front plate (5 x 20) T 5.0 A 00 0130 41<br />
Output fuse, bottom 15 A FKS 00 0132 02<br />
Clamp for mains connection, 3-pole 00 0211 40<br />
Clamp for 24 V connection, 4-pole 00 0211 41<br />
Clamp for control and indicator outputs, 7-pole 00 0211 39<br />
Bridging contact EB 2 – 5 for control clamps "x“ and "y“ 00 0223 56<br />