Power supply unit UPS 60, Or<strong>de</strong>r No. 77 3400 10<br />
• Charge status too low.<br />
• Battery fuse has failed.<br />
• Battery not correctly connected.<br />
• Battery is <strong>de</strong>fective.<br />
• Battery is too old, and must be replaced.<br />
3. Commissioning<br />
1. Connect input, output and battery terminal connections (refer to items 2.1 and 2.2).<br />
2. Switch on the input voltage (115 – 230 Volt).<br />
From now on, the connected nurse call system <strong>de</strong>vices are supplied with 24 V DC.<br />
3. The green LED "Power" is on due to the voltage at the terminal clamps.<br />
If the red LED "Battery low“ is on, the UPS function is not yet active<br />
(Place the bridging contact x – y).<br />
4. Now the power supply unit UPS is fully operational.<br />
4. Shutting the power supply UPS 60 off<br />
1. Shut off the input voltage (115 – 230 Volt).<br />
2. Remove the UPS function acc. to item 2.3.1 (Remove the bridging contact), otherwise the load for<br />
the user circuits will be supplied through the battery until the total discharge circuit disconnects the<br />
battery.<br />
5. Service<br />
To ensure the safe function of the system, batteries should be replaced every 3 years - <strong>de</strong>pending on<br />
the ambient temperature (Refer to diagram 1, Item 6). After 3 – 5 years, the battery capacity has<br />
dropped to approx. 60%.<br />
6. Battery service life<br />
The batteries connected to the power supply unit UPS 60 are sealed, service-free and rechargeable<br />
lead-gel batteries VRLA. According to the EUROBAT classification, these batteries have a useful<br />
service life of 5 – 7 years. This time, however, strongly <strong>de</strong>pends on the relevant ambient temperature.<br />
(Up to 20 °C: 7 – 8 years as shown in diagram 1)<br />
If the system will not be used for an exten<strong>de</strong>d period of time, the batteries should be fully charged to<br />
prevent a total discharge. (Refer to item 7 "Storage") While the system is not used, the battery fuse<br />
has to be removed to prevent total discharge.<br />