Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
Table 27 Liebert Challenger 3000 , Liebert Deluxe System/3 , Liebert Himod , Liebert ICS <br />
- Input <strong>and</strong> Holding - LAM<br />
Controller Advanced Microprocessor - LAM<br />
Liebert Products<br />
Liebert Challenger 3000<br />
Liebert Deluxe System/3<br />
Liebert Himod (LNA version - Using Liebert Sitescan ® )<br />
Liebert ICS<br />
Available Points<br />
Input Holding # of<br />
Data Description<br />
Status Points (View)<br />
Register Register Reg. Scale Notes / Units<br />
Temperature - 40001 1 - -<br />
Humidity - 40002 1 - -<br />
Cooling - 40003 1 - 1=On / 0=Off<br />
Heating - 40004 1 - 1=On / 0=Off<br />
Humidification - 40005 1 - 1=On / 0=Off<br />
De-humidification - 40006 1 - 1=On / 0=Off<br />
Econ-O-Cycle - 40007 1 - 1=On / 0=Off<br />
Stages - 40008 1 - -<br />
% Capacity - 40009 1 - -<br />
Unit Status (On / Off) - 40018 1 - 1=On / 0=Off (R/W)<br />
Analog input 1 - 40023 1 - A/D raw value w/ slope=1 <strong>and</strong> offset = 0<br />
Analog input 2 - 40024 1 - A/D raw value w/ slope=1 <strong>and</strong> offset = 0<br />
Analog input 3 - 40025 1 - A/D raw value w/ slope=1 <strong>and</strong> offset = 0<br />
Analog input 4 - 40026 1 - A/D raw value w/ slope=1 <strong>and</strong> offset = 0<br />
Alarm Points<br />
Discrete alarm objects available;<br />
use autodiscover for this unit<br />
Communications - 40289 1 - Bit 0<br />
Local Off - 40289 1 - Bit 1<br />
Remote Off - 40289 1 - Bit 2<br />
High Head Pressure 1 - 40289 1 - Bit 3<br />
High Head Pressure 2 - 40289 1 - Bit 4<br />
Loss of Airflow - 40289 1 - Bit 5<br />
St<strong>and</strong>by Glycol Unit On - 40289 1 - Bit 6<br />
Liquid Detected - 40289 1 - Bit 7<br />
Change Filters - 40289 1 - Bit 8<br />
High Temperature - 40289 1 - Bit 9<br />
Low Temperature - 40289 1 - Bit 10<br />
High Humidity - 40290 1 - Bit 0<br />
Low Humidity - 40290 1 - Bit 1<br />
Humidifier Problem - 40290 1 - Bit 2<br />
No Water in Humidifier Pan - 40290 1 - Bit 3<br />
Compressor 1 Overload - 40290 1 - Bit 4<br />
Compressor 2 Overload - 40290 1 - Bit 5<br />
Main Fan Overload - 40290 1 - Bit 6<br />
Manual Override - 40290 1 - Bit 7<br />
Smoke Detected - 40290 1 - Bit 8<br />
Loss of Water - 40290 1 - Bit 9<br />
St<strong>and</strong>by Unit On - 40290 1 - Bit 10<br />
Low Suction - 40291 1 - Bit 0<br />
Short Cycle - 40291 1 - Bit 1<br />
Loss of Power - 40291 1 - Bit 2<br />
99