<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
Table 7 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />
DS, Liebert HPM, Liebert PeX - Input <strong>and</strong> Holding (continued)<br />
Data Description<br />
Controller Liebert iCOM v4<br />
Input<br />
Register<br />
Remote Sensor Over Temp Threshold 30765 40765 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Under Temp Threshold 30506 40506 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Under Temp Threshold 30766 40766 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Average Temperature 30507 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Average Temperature 30767 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Maximum Temperature 30508 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Maximum Temperature 30768 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor System Average Temperature 30509 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor System Average Temperature 30769 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor System Maximum Temperature 30510 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor System Maximum Temperature 30770 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 1 30551 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 1 30771 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 2 30552 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 2 30772 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 3 30553 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 3 30773 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 4 30554 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 4 30774 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 5 30555 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 5 30775 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 6 30556 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 6 30776 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 7 30557 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 7 30777 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 8 30558 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 8 30778 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 9 30559 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 9 30779 - 1 x / 10 deg F 2, 3, 4<br />
Remote Sensor Temperature 10 30560 - 1 x / 10 deg C 2, 3, 4<br />
Remote Sensor Temperature 10 30780 - 1 x / 10 deg F 2, 3, 4<br />
Air Economizer Availability 30561 - 1 -<br />
20<br />
Holding<br />
Register<br />
# of<br />
Reg. Scale Units/Notes<br />
0 = Not Available<br />
1 = Available<br />
Extra<br />
Notes<br />
2, 3, 4<br />
Air Economizer Control Source 30562 40562 1 -<br />
0 = disabled<br />
1 = internal<br />
2 = external<br />
2, 3, 4<br />
Chilled Water Valve Hours 30563 40563 1 - hr 2, 3, 4<br />
Cooling Capacity 30564 - 1 - % 2, 3, 4<br />
Cooling Control Temperature 30565 - 1 x / 10 deg C 2, 3, 4<br />
Cooling Control Temperature 30781 - 1 x / 10 deg F 2, 3, 4<br />
Fan Speed Control Temperature 30566 - 1 x / 10 deg C 2, 3, 4<br />
Fan Speed Control Temperature 30782 - 1 x / 10 deg F 2, 3, 4