Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input Holding<br />

Data Label<br />

XD System 14 Temperature Sensor 4<br />

Register Register # of Reg Scale Notes/Units<br />

Remote Sensor Temperature 31480 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 14 Secondary Fans<br />

31481 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31487 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 15 Temperature Sensor 1<br />

31488 41488 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31494 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 15 Temperature Sensor 2<br />

31495 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31501 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 15 Temperature Sensor 4<br />

31502 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31515 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 15 Secondary Fans<br />

31516 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31522 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 16 Temperature Sensor 1<br />

31523 41523 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31529 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 16 Temperature Sensor 2<br />

31530 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31536 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 16 Temperature Sensor 4<br />

31537 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31550 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 16 Secondary Fans<br />

31551 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31557 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 17 Temperature Sensor 1<br />

31558 41558 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31564 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 17 Temperature Sensor 2<br />

31565 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31571 1 Scale : x / 10 Units : deg C<br />