Table 18 Liebert XDP - Status <strong>and</strong> Coil<br />
Controller Liebert iCOM v4<br />
Data Label Status Coil Number of Bits Notes<br />
Pumps<br />
Pump 1 Loss of Flow 10001 1 Active on Alarm<br />
Pump 2 Loss of Flow 10002 1 Active on Alarm<br />
Pump Short Cycle<br />
System Events<br />
10020 1 Active on Alarm<br />
Fan Issue 10003 1 Active on Alarm<br />
System Condensation Detected 10004 1 Active on Alarm<br />
Customer Input 1 10005 1 Active on Alarm<br />
Shutdown - Loss Of Power 10019 1 Active on Alarm<br />
Water Under Floor 10021 1 Active on Alarm<br />
Smoke Detected 10022 1 Active on Alarm<br />
Service Required 10023 1 Active on Alarm<br />
Unit Communication Lost 10262 1 Active on Alarm<br />
RAM Battery Issue 10263 1 Active on Alarm<br />
Master Unit Communication Lost 10264 1 Active on Alarm<br />
Remote Shutdown 10265 1 Active on Alarm<br />
Unit Code Missing<br />
Chilled Water<br />
10266 1 Active on Alarm<br />
Supply Chilled Water Over Temp 10006 1 Active on Alarm<br />
Supply Chilled Water Temp Sensor Issue 10007 1 Active on Alarm<br />
Chilled Water Control Valve Position<br />
Refrigerant<br />
10018 1 Active on Alarm<br />
Supply Refrigerant Over Temp 10008 1 Active on Alarm<br />
Supply Refrigerant Under Temp 10009 1 Active on Alarm<br />
Supply Refrigerant Temp Sensor Issue<br />
External Air<br />
10010 1 Active on Alarm<br />
Ext Air Sensor A Over Temperature 10011 1 Active on Alarm<br />
Ext Air Sensor A Under Temperature 10012 1 Active on Alarm<br />
Ext Air Sensor A Issue 10013 1 Active on Alarm<br />
Ext Air Sensor B Over Temperature 10014 1 Active on Alarm<br />
Ext Air Sensor B Under Temperature 10015 1 Active on Alarm<br />
Ext Air Sensor B Issue 10016 1 Active on Alarm<br />
Ext Dew Point Over Temperature<br />
Pump Hours 1<br />
10017 1 Active on Alarm<br />
Pump Hours Exceeded<br />
Pump Hours 2<br />
10030 1 Active on Alarm<br />
Pump Hours Exceeded<br />
XD System 1<br />
10036 1 Active on Alarm<br />
Ext System Condensation Detected 10042 1 Active on Alarm<br />
Ext Fan Issue 10043 1 Active on Alarm<br />
Sensor Issue 10044 1 Active on Alarm<br />
Ext Remote Shutdown 10045 1 Active on Alarm<br />
Hot Aisle Temp Out of Range 10046 1 Active on Alarm<br />
Cold Aisle Temp Out of Range<br />
XD System 2<br />
10047 1 Active on Alarm<br />
Ext System Condensation Detected 10053 1 Active on Alarm<br />