Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Table 10 Liebert CRV - Input <strong>and</strong> Holding<br />
Controller Liebert iCOM v4<br />
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
Input Holding # of<br />
Data Description<br />
Register Register Reg. Scale Notes / Units<br />
Supply Air Temperature 30385 - 1 x / 10 deg C<br />
Supply Air Temperature 30386 - 1 x / 10 deg F<br />
Return Air Temperature 30387 - 1 x / 10 deg C<br />
Return Air Temperature 30388 - 1 x / 10 deg F<br />
Return Dew Point 30389 - 1 x / 10 deg C<br />
Return Dew Point 30390 - 1 x / 10 deg F<br />
Remote Sensor Minimum Temperature 30391 - 1 x / 10 deg C<br />
Remote Sensor Minimum Temperature 30392 - 1 x / 10 deg F<br />
Remote Sensor Maximum Temperature 30393 - 1 x / 10 deg C<br />
Remote Sensor Maximum Temperature 30394 - 1 x / 10 deg F<br />
Remote Sensor Average Temperature 30395 - 1 x / 10 deg C<br />
Remote Sensor Average Temperature 30396 - 1 x / 10 deg F<br />
Air Temperature Set Point 30397 40397 1 x / 10 deg C<br />
Air Temperature Set Point 30398 40398 1 x / 10 deg F<br />
Cooling Proportional B<strong>and</strong> 30399 40399 1 x / 10 deg C<br />
Cooling Proportional B<strong>and</strong> 30400 40400 1 x / 10 deg F<br />
Heating Proportional B<strong>and</strong> 30401 40401 1 x / 10 deg C<br />
Heating Proportional B<strong>and</strong> 30402 40402 1 x / 10 deg F<br />
Air Temperature Dead B<strong>and</strong> 30403 40403 1 x / 10 deg C<br />
Air Temperature Dead B<strong>and</strong> 30404 40404 1 x / 10 deg F<br />
Supply Air Over Temp Threshold 30405 40405 1 x / 10 deg C<br />
Supply Air Over Temp Threshold 30406 40406 1 x / 10 deg F<br />
Supply Air Under Temp Threshold 30407 40407 1 x / 10 deg C<br />
Supply Air Under Temp Threshold 30408 40408 1 x / 10 deg F<br />
Return Air Over Temp Threshold 30409 40409 1 x / 10 deg C<br />
Return Air Over Temp Threshold 30410 40410 1 x / 10 deg F<br />
Supply Humidity 30411 - 1 x / 10 % RH<br />
Return Humidity 30412 - 1 x / 10 % RH<br />
Humidity Set Point 30413 40413 1 - % RH<br />
Humidification Proportional B<strong>and</strong> 30414 40414 1 - % RH<br />
Dehumidification Proportional B<strong>and</strong> 30415 40415 1 - % RH<br />
Humidity Dead B<strong>and</strong> 30416 40416 1 x / 10 % RH<br />
High Return Humidity Threshold 30417 40417 1 x / 10 % RH<br />
Low Return Humidity Threshold 30418 40418 1 x / 10 % RH<br />
Fan Speed Proportional B<strong>and</strong> 30419 40419 1 x / 10 deg C<br />
Fan Speed Proportional B<strong>and</strong> 30420 40420 1 x / 10 deg F<br />
Fan Speed Manual Set Point 30421 40421 1 - %<br />
Fan Speed Maximum Set Point 30422 40422 1 - %<br />
Fan Speed Minimum Set Point 30423 40423 1 - %<br />
Remote Sensor Temperature 1 - 10<br />
30424-<br />
30433<br />
34<br />
- 1 x / 10 deg C<br />
Remote Sensor Temperature 1 - 10<br />
30434-<br />
30443<br />
- 1 x / 10 deg F<br />
Supply Chilled Water Temperature 30444 - 1 x / 10 deg C<br />
Supply Chilled Water Temperature 30445 - 1 x / 10 deg F<br />
Supply Chilled Water Over Temp Threshold 30446 40446 1 x / 10 deg C<br />
Supply Chilled Water Over Temp Threshold 30447 40447 1 x / 10 deg F<br />
BMS Timeout Period 30448 40448 1 - min