220<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 73 Liebert CRV - Binary Data<br />

Controller Liebert iCOM v4<br />

Data Description<br />

Air Temperature<br />

Object Type Instance<br />

Object<br />

Name Access Notes<br />

Supply Air Over Temperature Binary_Value 1 5015_1 RD Active on Alarm<br />

Supply Air Under Temperature Binary_Value 2 5019_1 RD Active on Alarm<br />

Return Air Over Temperature Binary_Value 3 5023_1 RD Active on Alarm<br />

Supply Air Sensor Issue Binary_Value 4 5026_1 RD Active on Alarm<br />

Return Air Sensor Issue<br />

Humidity<br />

Binary_Value 5 5147_1 RD Active on Alarm<br />

High Return Humidity Binary_Value 16 5034_1 RD Active on Alarm<br />

Low Return Humidity Binary_Value 17 5036_1 RD Active on Alarm<br />

Humidifier Hours Exceeded Binary_Value 18 5037_1 RD Active on Alarm<br />

Dehumidifier Hours Exceeded Binary_Value 19 5038_1 RD Active on Alarm<br />

Humidifier Under Current Binary_Value 20 5039_1 RD Active on Alarm<br />

Humidifier Over Current Binary_Value 21 5040_1 RD Active on Alarm<br />

Humidifier Low Water Binary_Value 22 5041_1 RD Active on Alarm<br />

Humidifier Cylinder Worn Binary_Value 23 5042_1 RD Active on Alarm<br />

Humidifier Issue Binary_Value 24 5043_1 RD Active on Alarm<br />

Ext Humidifier Lockout Binary_Value 25 5044_1 RD Active on Alarm<br />

Humidifier Control Board Not Detected Binary_Value 26 5045_1 RD Active on Alarm<br />

Return Humidity Out Of Proportional B<strong>and</strong><br />

Fans<br />

Binary_Value 27 5046_1 RD Active on Alarm<br />

Loss of Air Flow Binary_Value 38 5053_1 RD Active on Alarm<br />

Fan Hours Exceeded Binary_Value 39 5054_1 RD Active on Alarm<br />

Top Fan Issue Binary_Value 40 5055_1 RD Active on Alarm<br />

Bottom Fan Issue<br />

Remote Sensors 1<br />

Binary_Value 41 5056_1 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 2<br />

Binary_Value 52 5060_1 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 3<br />

Binary_Value 63 5060_2 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 4<br />

Binary_Value 74 5060_3 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 5<br />

Binary_Value 85 5060_4 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 6<br />

Binary_Value 96 5060_5 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 7<br />

Binary_Value 107 5060_6 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 8<br />

Binary_Value 118 5060_7 RD Active on Alarm<br />

Remote Sensor Issue<br />

Remote Sensors 9<br />

Binary_Value 129 5060_8 RD Active on Alarm<br />

Remote Sensor Issue Binary_Value 140 5060_9 RD Active on Alarm