Table 78 Liebert HPC - Analog Data (continued)<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

241<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Object<br />

Name Access Notes<br />

Supply Fluid Temperature Analog_Value 164 4643_1 RD Units: deg C 1, 2<br />

Supply Fluid Temperature Analog_Value 10164 4643_1_deg_F RD Units: deg F 1, 2<br />

Actual Supply Fluid Temp Set Point Analog_Value 165 5282_1 RD Units: deg C 1, 2<br />

Actual Supply Fluid Temp Set Point Analog_Value 10165 5282_1_deg_F RD Units: deg F 1, 2<br />

Condenser Inlet Water Temperature Analog_Value 166 5517_1 RD Units: deg C 1, 2<br />

Condenser Inlet Water Temperature Analog_Value 10166 5517_1_deg_F RD Units: deg F 1, 2<br />

Condenser Outlet Water Temperature Analog_Value 167 5518_1 RD Units: deg C 1, 2<br />

Condenser Outlet Water Temperature Analog_Value 10167 5518_1_deg_F RD Units: deg F 1, 2<br />

Supply Heated Water Temp Set Point Analog_Value 168 5313_1 RW Units: deg C 1, 2<br />

Supply Heated Water Temp Set Point Analog_Value 10168 5313_1_deg_F RW Units: deg F 1, 2<br />

Free Cooling Utilization Analog_Value 169 5519_1 RD Units: % 1, 2<br />

Reheat Utilization Analog_Value 170 5080_1 RD Units: % 1, 2<br />

Compressor Utilization Analog_Value 171 5078_1 RD Units: % 1, 2<br />

Ambient Air Temperature Analog_Value 172 4594_1 RD Units: deg C 1, 2<br />

Ambient Air Temperature Analog_Value 10172 4594_1_deg_F RD Units: deg F 1, 2<br />

Compressor Economizer Utilization Analog_Value 173 5520_1 RD Units: % 1, 2<br />

Condenser Adiabatic Cooling Utilization<br />

Time<br />

Analog_Value 174 5521_1 RD Units: % 1, 2<br />

System Date <strong>and</strong> Time Analog_Value 185 4293_1 RW 1, 2<br />

1. This point is supported on iCOM_SC31<br />

2. This point is supported on iCOM_SC100<br />