Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
Table 31 Liebert Atlas Air , Liebert Atlas PEC , Liebert LECS 15 - Input <strong>and</strong><br />
Holding - C10 2-step (continued)<br />
Controller C10<br />
Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert LECS 15<br />
Available Points<br />
Input Holding # of<br />
Data Description Register Register Reg. Scale Notes / Units<br />
Setpoints (View)<br />
Return Air Temperature - 40016 1 10 deg C (R/W)<br />
Return Air Humidity - 40017 1 10 deg C (R/W)<br />
Supply Air Temperature - 40018 1 10 deg C (R/W)<br />
High Temp Alarm - 40025 1 10 deg C (R/W)<br />
Low Temp Alarm - 40026 1 10 deg C (R/W)<br />
High Hum Alarm - 40027 1 10 % (R/W)<br />
Low Hum Alarm - 40028 1 10 % (R/W)<br />
Restart Delay<br />
Control Points (Set)<br />
- 40029 1 - Seconds (R/W)<br />
Activation Mode - 40006 1 - 1=On / 0=Off (R/W)<br />
General Alarm Status - 40022 1 - 1=On / 0=Off; write 0 to reset alarm<br />
Audible Alarm Status - 40023 1 - 1=On / 0=Off; write 0 to ack alarm<br />
Return Air Temperature - 40349 1 10 deg C (R/W)<br />
Return Air Humidity - 40350 1 10 deg C (R/W)<br />
Supply Air Temperature - 40351 1 10 deg C (R/W)<br />
If the Scale column has a value for a Data Description, multiply the <strong>Modbus</strong> value by the value in the Scale column.<br />
Table 32 Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input <strong>and</strong><br />
Holding - C100 4-step<br />
Controller CEMS 100<br />
Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert CEMS 100<br />
Available Points<br />
Input Holding # of<br />
Data Description<br />
Status Points (View)<br />
Register Register Reg. Scale Notes / Units<br />
Unit Number - 40001 1 - 1-99<br />
Average Return Air Temp. - 40002 1 10 deg C<br />
Average Return Air Humidity - 40003 1 10 %<br />
Average Supply Air Temp. - 40004 1 10 deg C<br />
Average Supply Air Humidity - 40005 1 10 %<br />
Fan Status - 40007 1 - 1=On / 0=Off<br />
Cool 1 Status - 40008:0 1 - 1=On / 0=Off<br />
Cool 2 Status - 40009:0 1 - 1=On / 0=Off<br />
Cool 3 Status - 40008:4 1 - 1=On / 0=Off<br />
Cool 4 Status - 40009:4 1 - 1=On / 0=Off<br />
Heat 1 Status - 40010 1 - 1=On / 0=Off<br />
Heat 2 Status - 40011 1 - 1=On / 0=Off<br />
Humidifier Status - 40012 1 - -<br />
De-humidifier Status - 40013 1 - -<br />
107