Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 31 Liebert Atlas Air , Liebert Atlas PEC , Liebert LECS 15 - Input <strong>and</strong><br />

Holding - C10 2-step (continued)<br />

Controller C10<br />

Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert LECS 15<br />

Available Points<br />

Input Holding # of<br />

Data Description Register Register Reg. Scale Notes / Units<br />

Setpoints (View)<br />

Return Air Temperature - 40016 1 10 deg C (R/W)<br />

Return Air Humidity - 40017 1 10 deg C (R/W)<br />

Supply Air Temperature - 40018 1 10 deg C (R/W)<br />

High Temp Alarm - 40025 1 10 deg C (R/W)<br />

Low Temp Alarm - 40026 1 10 deg C (R/W)<br />

High Hum Alarm - 40027 1 10 % (R/W)<br />

Low Hum Alarm - 40028 1 10 % (R/W)<br />

Restart Delay<br />

Control Points (Set)<br />

- 40029 1 - Seconds (R/W)<br />

Activation Mode - 40006 1 - 1=On / 0=Off (R/W)<br />

General Alarm Status - 40022 1 - 1=On / 0=Off; write 0 to reset alarm<br />

Audible Alarm Status - 40023 1 - 1=On / 0=Off; write 0 to ack alarm<br />

Return Air Temperature - 40349 1 10 deg C (R/W)<br />

Return Air Humidity - 40350 1 10 deg C (R/W)<br />

Supply Air Temperature - 40351 1 10 deg C (R/W)<br />

If the Scale column has a value for a Data Description, multiply the <strong>Modbus</strong> value by the value in the Scale column.<br />

Table 32 Liebert Atlas Air, Liebert Atlas PEC, Liebert CEMS 100 - Input <strong>and</strong><br />

Holding - C100 4-step<br />

Controller CEMS 100<br />

Liebert Products Liebert Atlas Air; Liebert Atlas PEC; Liebert CEMS 100<br />

Available Points<br />

Input Holding # of<br />

Data Description<br />

Status Points (View)<br />

Register Register Reg. Scale Notes / Units<br />

Unit Number - 40001 1 - 1-99<br />

Average Return Air Temp. - 40002 1 10 deg C<br />

Average Return Air Humidity - 40003 1 10 %<br />

Average Supply Air Temp. - 40004 1 10 deg C<br />

Average Supply Air Humidity - 40005 1 10 %<br />

Fan Status - 40007 1 - 1=On / 0=Off<br />

Cool 1 Status - 40008:0 1 - 1=On / 0=Off<br />

Cool 2 Status - 40009:0 1 - 1=On / 0=Off<br />

Cool 3 Status - 40008:4 1 - 1=On / 0=Off<br />

Cool 4 Status - 40009:4 1 - 1=On / 0=Off<br />

Heat 1 Status - 40010 1 - 1=On / 0=Off<br />

Heat 2 Status - 40011 1 - 1=On / 0=Off<br />

Humidifier Status - 40012 1 - -<br />

De-humidifier Status - 40013 1 - -<br />