20.12.2012 Views

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Power Distribution <strong>and</strong> Power Conditioning Products<br />

Table 36 Liebert EXC, Liebert FDC, Liebert FPC, Liebert RDC, Liebert PPC, Liebert RX - Input <strong>and</strong><br />

Holding (continued)<br />

Data Description<br />

Controller v4<br />

Liebert Products Liebert EXC, Liebert FDC, Liebert FPC, Liebert PPC, Liebert RDC, Liebert RX<br />

Available Points<br />

Input<br />

Register<br />

Holding<br />

Register<br />

Panel Main Current Ix 30471 - 1 - A AC<br />

Panel Main Current Iy 30472 - 1 - A AC<br />

Panel Main Current Iz 30473 - 1 - A AC<br />

Panel Main Neutral Current 30474 - 1 - A AC<br />

Panel Main Ground Current 30475 - 1 10 A AC<br />

Panel Main Output Power (kVA) 30476 - 1 - kVA<br />

Panel Main Output Power (kW) 30477 - 1 - kW<br />

Panel Main Output kW-Hrs 30478 40478 2 10 kWH<br />

Panel Main Output Power Factor 30480 - 1 100 -<br />

Panel Main Output Percent Load 30481 - 1 - %<br />

Panel Main Voltage Vx THD 30482 - 1 10 % THD<br />

Panel Main Voltage Vy THD 30483 - 1 10 % THD<br />

Panel Main Voltage Vz THD 30484 - 1 10 % THD<br />

Panel Main Current Ix THD 30<strong>485</strong> - 1 10 % THD<br />

Panel Main Current Iy THD 30486 - 1 10 % THD<br />

Panel Main Current Iz THD 30487 - 1 10 % THD<br />

Panel Main Current Ix Crest Factor 30488 - 1 10 -<br />

Panel Main Current Iy Crest Factor 30489 - 1 10 -<br />

Panel Main Current Iz Crest Factor<br />

Panel 2<br />

30490 - 1 10 -<br />

Columns of Breakers 30494 - 1 - -<br />

Number of Breakers 30495 - 1 - -<br />

Panel Main Voltage X-Y 30496 - 1 - VAC<br />

Panel Main Voltage Y-Z 30497 - 1 - VAC<br />

Panel Main Voltage Z-X 30498 - 1 - VAC<br />

Panel Main Voltage X-N 30499 - 1 - VAC<br />

Panel Main Voltage Y-N 30500 - 1 - VAC<br />

Panel Main Voltage Z-N 30501 - 1 - VAC<br />

Panel Main Current Ix 30502 - 1 - A AC<br />

Panel Main Current Iy 30503 - 1 - A AC<br />

Panel Main Current Iz 30504 - 1 - A AC<br />

Panel Main Neutral Current 30505 - 1 - A AC<br />

Panel Main Ground Current 30506 - 1 10 A AC<br />

Panel Main Output Power (kVA) 30507 - 1 - kVA<br />

Panel Main Output Power (kW) 30508 - 1 - kW<br />

Panel Main Output kW-Hrs 30509 40509 2 10 kWH<br />

Panel Main Output Power Factor 30511 - 1 100 -<br />

Panel Main Output Percent Load 30512 - 1 - %<br />

Panel Main Voltage Vx THD 30513 - 1 10 % THD<br />

118<br />