3.0 MODBUS <strong>485</strong> AND MODBUS <strong>IP</strong> PROTOCOLS<br />

3.1 Precision Cooling Products<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 6 Liebert Challenger 3000, Liebert Challenger ITR , Liebert CW , Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM , Liebert PeX - Status <strong>and</strong> Coil<br />

Controller Liebert iCOM v4<br />

Liebert Products<br />

Units with<br />

Liebert iCOM:<br />

Liebert HPM<br />

6<br />

Units with Liebert iCOM Firmware<br />

PA1.04.033.STD or later:<br />

Liebert Challenger 3000<br />

Liebert Challenger ITR<br />

Liebert CW<br />

Liebert Deluxe System/3<br />

Liebert DS<br />

Liebert PeX<br />

Available Points<br />

Data Description Status Coil # of Bits Notes Extra Notes<br />

Ext Reheat Lockout 10009 - 1 Active on Alarm 1, 2, 3, 4<br />

Ext Humidifier Lockout 10010 - 1 Active on Alarm 1, 2, 3, 4<br />

Minimum Chilled Water Temp Set Point Enable 10013 13 1<br />

Return Air Sensor Event Control 10019 19 1<br />

0 = disabled<br />

1 = enabled<br />

0 = disabled<br />

1 = enabled<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

Ext Air Sensor A Event Control 10020 20 1<br />

0 = disabled<br />

1 = enabled<br />

1, 2, 3, 4<br />

Ext Compressor Lockout 10021 - 1 Active on Alarm 1, 2, 3, 4<br />

System On/Off Control - 25 1<br />

Fan State 10025 - 1<br />

Cooling State 10026 - 1<br />

Free Cooling State 10027 - 1<br />

Hot Water / Hot Gas State 10028 - 1<br />

Electric Reheat State 10029 - 1<br />

Humidifier State 10030 - 1<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

0 = off<br />

1 = on<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

1, 2, 3, 4<br />

Dehumidifier State 10031 - 1<br />

0 = off<br />

1 = on<br />

1, 2, 3, 4<br />

Main Fan Overload 10034 - 1 Active on Alarm 1, 2, 3, 4<br />

Loss of Air Flow 10035 - 1 Active on Alarm 1, 2, 3, 4<br />

Ext Loss of Flow 10036 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor High Head Pressure 10037 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Low Suction Pressure 10038 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Thermal Overload 10039 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Pump Down Issue 10040 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor High Head Pressure 2 10041 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Low Suction Pressure 2 10042 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Thermal Overload 2 10043 - 1 Active on Alarm 1, 2, 3, 4<br />

Compressor Pump Down Issue 2 10044 - 1 Active on Alarm 1, 2, 3, 4