4.3 UPS Systems<br />

Table 87 Liebert APM - Binary Data<br />

267<br />

<strong>BACnet</strong> Communications - UPS Systems<br />

Data Description<br />

System Status<br />

Object Type Instance<br />

Object<br />

Name Access Notes<br />

Battery Auto Test In Progress Binary_Value 1 4172_1 RD Active on Alarm<br />

Battery Equalize Binary_Value 2 4170_1 RD Active on Alarm<br />

Battery Charging Inhibited Binary_Value 3 4200_1 RD Active on Alarm<br />

On Generator<br />

System Events<br />

Binary_Value 4 4315_1 RD Active on Alarm<br />

System Input Power Problem Binary_Value 15 4122_1 RD Active on Alarm<br />

Rectifier Failure Binary_Value 16 4295_1 RD Active on Alarm<br />

Inverter Failure Binary_Value 17 4233_1 RD Active on Alarm<br />

Bypass Not Available Binary_Value 18 4135_1 RD Active on Alarm<br />

Battery Low Binary_Value 19 4162_1 RD Active on Alarm<br />

LBS Inhibited Binary_Value 20 4758_1 RD Active on Alarm<br />

System Fan Failure Binary_Value 21 4311_1 RD Active on Alarm<br />

Equipment Over Temperature Binary_Value 22 4310_1 RD Active on Alarm<br />

System Shutdown - EPO Binary_Value 23 4213_1 RD Active on Alarm<br />

Bypass Static Switch Unavailable Binary_Value 24 4143_1 RD Active on Alarm<br />

Bypass - Excess Auto Retransfers Binary_Value 25 4139_1 RD Active on Alarm<br />

Parallel Comm Warning Binary_Value 26 4823_1 RD Active on Alarm<br />

Power Supply Failure Binary_Value 27 4314_1 RD Active on Alarm<br />

Battery Over Temperature Binary_Value 28 4219_1 RD Active on Alarm<br />

System Input Phs Rotation Error Binary_Value 29 4146_1 RD Active on Alarm<br />

Fuse Failure Binary_Value 30 4440_1 RD Active on Alarm<br />

Inverter Overload Phase A Binary_Value 31 4234_1 RD Active on Alarm<br />

Inverter Overload Phase B Binary_Value 32 4235_1 RD Active on Alarm<br />

Inverter Overload Phase C Binary_Value 33 4236_1 RD Active on Alarm<br />

MMS Overload Binary_Value 34 4831_1 RD Active on Alarm<br />

Inverter Shutdown - Overload Binary_Value 35 4290_1 RD Active on Alarm<br />

System Output Fault Binary_Value 36 4389_1 RD Active on Alarm<br />

Internal Communications Failure Binary_Value 37 4300_1 RD Active on Alarm<br />

Battery Charging Error Binary_Value 38 4164_1 RD Active on Alarm<br />

System Input Current Imbalance Binary_Value 39 4382_1 RD Active on Alarm<br />

Main Battery Disconnect Open Binary_Value 40 4173_1 RD Active on Alarm<br />

Inverter Static Switch SCR Short Binary_Value 41 4391_1 RD Active on Alarm<br />

Battery Not Qualified Binary_Value 42 5149_1 RD Active on Alarm<br />

Battery Terminals Reversed Binary_Value 43 5150_1 RD Active on Alarm<br />

Battery Converter Failure Binary_Value 44 5151_1 RD Active on Alarm<br />

Inverter SCR Open Binary_Value 45 5152_1 RD Active on Alarm<br />

Load Sharing Fault Binary_Value 46 5153_1 RD Active on Alarm<br />

DC Bus Abnormal Binary_Value 47 5154_1 RD Active on Alarm<br />

Mains Input Neutral Lost Binary_Value 48 5155_1 RD Active on Alarm<br />

Load Impact Transfer Binary_Value 49 5156_1 RD Active on Alarm