Table 16 Liebert XDC - Input <strong>and</strong> Holding (continued)<br />

Controller Liebert iCOM v4<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input Holding # of<br />

Data Description<br />

Register Register Reg. Scale Notes / Units<br />

External Air<br />

Ext Air Sensor A Temperature 30390 1 Scale: x / 10 Units : deg C<br />

Ext Air Sensor A Temperature 30391 1 Scale: x / 10 Units : deg F<br />

Ext Air Sensor A Humidity 30392 1 Scale: x / 10 Units : % RH<br />

Ext Air Sensor A Dew Point Temp 30393 1 Scale: x / 10 Units : deg C<br />

Ext Air Sensor A Dew Point Temp 30394 1 Scale: x / 10 Units : deg F<br />

Ext Air Sensor B Temperature 30395 1 Scale: x / 10 Units : deg C<br />

Ext Air Sensor B Temperature 30396 1 Scale: x / 10 Units : deg F<br />

Ext Air Sensor B Humidity 30397 1 Scale: x / 10 Units : % RH<br />

Ext Air Sensor B Dew Point Temp 30398 1 Scale: x / 10 Units : deg C<br />

Ext Air Sensor B Dew Point Temp 30399 1 Scale: x / 10 Units : deg F<br />

Dew Point Temperature 30400 1 Scale: x / 10 Units : deg C<br />

Dew Point Temperature 30401 1 Scale: x / 10 Units : deg F<br />

Minimum Room Temperature Set Point 30402 40402 1 Scale: x / 10 Units : deg C<br />

Minimum Room Temperature Set Point 30403 40403 1 Scale: x / 10 Units : deg F<br />

Ext Air Over Temp Threshold 30404 40404 1 Scale: x / 10 Units : deg C<br />

Ext Air Over Temp Threshold 30405 40405 1 Scale: x / 10 Units : deg F<br />

Ext Air Under Temp Threshold 30406 40406 1 Scale: x / 10 Units : deg C<br />

Ext Air Under Temp Threshold 30407 40407 1 Scale: x / 10 Units : deg F<br />

Ext Dew Point Over Temp Threshold 30408 40408 1 Scale: x / 10 Units : deg C<br />

Ext Dew Point Over Temp Threshold<br />

Hot Gas<br />

30409 40409 1 Scale: x / 10 Units : deg F<br />

Hot Gas Valve 1 Open Position 30412 1 Scale : x / 10 Units : %<br />

Hot Gas Valve 2 Open Position 30413 1 Scale : x / 10 Units : %<br />

Hot Gas Solenoid Valve 1 Position 30414 1<br />

0 = closed<br />

1 = open<br />

Hot Gas Solenoid Valve 2 Position<br />

Compressors<br />

30415 1<br />

0 = closed<br />

1 = open<br />

Compressor 1A State 30416 1<br />

0 = off<br />

1 = on<br />

Compressor 1B State 30417 1<br />

0 = off<br />

1 = on<br />

Compressor 2A State 30418 1<br />

0 = off<br />

1 = on<br />

Compressor 2B State<br />

Pump Hours 1<br />

30419 1<br />

0 = off<br />

1 = on<br />

Pump Hours 30430 40430 1 Units : hr<br />

Pump Hours Threshold<br />

Pump Hours 2<br />

30431 40431 1 Units : hr<br />

Pump Hours 30437 40437 1 Units : hr<br />

Pump Hours Threshold 30438 40438 1 Units : hr<br />