Table 52 Liebert NXL SA, SR, SN, MM, CD - Input <strong>and</strong> Holding (continued) Data Label Battery Cell Count-Nickel Cadmium Input Register Holding Register 30355 - 1 - UPS System Output Source 30356 - 1 - 156 <strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems 0 = Off 1 = Normal 2 = Bypass 3 = Maintenance Bypass Static Bypass Switch 30357 - 1 - 0 = off 1 = on Battery Volts for Cabinet 1 30358 - 1 - VDC Battery Volts for Cabinet 2 30359 - 1 - VDC Battery Volts for Cabinet 3 30360 - 1 - VDC Battery Volts for Cabinet 4 30361 - 1 - VDC Battery Volts for Cabinet 5 30362 - 1 - VDC Battery Volts for Cabinet 6 30363 - 1 - VDC Battery Volts for Cabinet 7 30364 - 1 - VDC Battery Volts for Cabinet 8 30365 - 1 - VDC Battery Temperature for Cabinet 1 30366 - 1 - deg C Battery Temperature for Cabinet 2 30367 - 1 - deg C Battery Temperature for Cabinet 3 30368 - 1 - deg C Battery Temperature for Cabinet 4 30369 - 1 - deg C Battery Temperature for Cabinet 5 30370 - 1 - deg C Battery Temperature for Cabinet 6 30371 - 1 - deg C Battery Temperature for Cabinet 7 30372 - 1 - deg C Battery Temperature for Cabinet 8 30373 - 1 - deg C Backfeed Breaker 30374 - 1 - SBS Load Disconnect 30375 - 1 - Input Breaker (CB1/RIB) 30376 - 1 - Trap Filter Disconnect 30377 - 1 - # of Regs Scale Units / Notes 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed NXL Types N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS Depricated N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS
Table 52 Liebert NXL SA, SR, SN, MM, CD - Input <strong>and</strong> Holding (continued) Output Breaker (CB2/IOB) 30378 - 1 - Internal Bypass Breaker (CB3) 30379 - 1 - Bypass Isolation Breaker (BIB) 30380 - 1 - Rectifier Feed Breaker (RFB) 30381 - 1 - Maintenance Bypass Breaker (MBB) Maintenance Isolation Breaker (MIB) 30382 - 1 - 30383 - 1 - Output Series Static Switch 30384 - 1 - Module Output Breaker (MOB) 30385 - 1 - 157 <strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed 0 = Open 1 = Close 2 = Not Installed Battery Amp-Hours Consumed 30386 - 2 - AH Auto Retransfer Time Remaining 30388 - 1 - sec Inverter On/Off State 30389 - 1 - UPS Battery Status 30390 - 1 - UPS Output Source 30391 - 1 - System Date <strong>and</strong> Time 39998 49998 2 - Environment 0 = off 1 = on 1 = Unknown 2 = Normal 3 = Low 4 = Depleted 1 = Other 2 = Off 3 = Normal 4 = Bypass 5 = Battery 6 = Booster 7 = Reducer Total kW Hours Saved 30491 2 Units : kWH System Date <strong>and</strong> Time 39998 49998 2 System Data Label Input Register Holding Register # of Regs Scale Units / Notes Secs since Epoch(UTC) NXL Types N+1, 1+N, 1+1, SMS Depricated 1+N, 1+1, SMS SMS SCC, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS LEU/LAP only SCC, 1+N, 1+1 N+1, 1+N, 1+1, SMS SCC, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS SCC, N+1, 1+N, 1+1, SMS
- Page 1:
Infrastructure Management & Monitor
- Page 4 and 5:
3.0 MODBUS 485 AND MODBUS IP PROTOC
- Page 6 and 7:
3.4 Battery Monitoring Products . .
- Page 8 and 9:
MODBUS 485 & MODBUS IP PROTOCOLS (c
- Page 10 and 11:
2.3.2 Function Code 4 Modbus Commun
- Page 12 and 13:
3.0 MODBUS 485 AND MODBUS IP PROTOC
- Page 14 and 15:
Modbus 485 and Modbus IP Protocols
- Page 16 and 17:
Modbus 485 and Modbus IP Protocols
- Page 18 and 19:
Modbus 485 and Modbus IP Protocols
- Page 20 and 21:
Modbus 485 and Modbus IP Protocols
- Page 22 and 23:
Shutdown - Loss Of Power - Event Ty
- Page 24 and 25:
Modbus 485 and Modbus IP Protocols
- Page 26 and 27:
Modbus 485 and Modbus IP Protocols
- Page 28 and 29:
Modbus 485 and Modbus IP Protocols
- Page 30 and 31:
Modbus 485 and Modbus IP Protocols
- Page 32 and 33:
Modbus 485 and Modbus IP Protocols
- Page 34 and 35:
Modbus 485 and Modbus IP Protocols
- Page 36 and 37:
Remote Sensor System Average Over T
- Page 38 and 39:
Modbus 485 and Modbus IP Protocols
- Page 40 and 41:
Table 10 Liebert CRV - Input and Ho
- Page 42 and 43:
Table 10 Liebert CRV - Input and Ho
- Page 44 and 45:
Table 10 Liebert CRV - Input and Ho
- Page 46 and 47:
Table 11 Liebert CRV - Glossary (co
- Page 48 and 49:
Table 11 Liebert CRV - Glossary (co
- Page 50 and 51:
Table 12 Liebert HPC (Chiller) - S
- Page 52 and 53:
Table 13 Liebert HPC (Chiller) - In
- Page 54 and 55:
Table 13 Liebert HPC (Chiller) - In
- Page 56 and 57:
Table 14 Liebert HPC (Chiller) - Gl
- Page 58 and 59:
Table 14 Liebert HPC (Chiller) - Gl
- Page 60 and 61:
Table 15 Liebert XDC - Status and
- Page 62 and 63:
Table 16 Liebert XDC - Input and Ho
- Page 64 and 65:
Table 16 Liebert XDC - Input and Ho
- Page 66 and 67:
Table 16 Liebert XDC - Input and Ho
- Page 68 and 69:
Table 16 Liebert XDC - Input and Ho
- Page 70 and 71:
Table 16 Liebert XDC - Input and Ho
- Page 72 and 73:
Table 17 Liebert XDC - Glossary (co
- Page 74 and 75:
Table 17 Liebert XDC - Glossary (co
- Page 76 and 77:
Modbus 485 and Modbus IP Protocols
- Page 78 and 79:
Table 19 Liebert XDP - Input and Ho
- Page 80 and 81:
Table 19 Liebert XDP - Input and Ho
- Page 82 and 83:
Table 19 Liebert XDP - Input and Ho
- Page 84 and 85:
Table 19 Liebert XDP - Input and Ho
- Page 86 and 87:
Table 19 Liebert XDP - Input and Ho
- Page 88 and 89:
Table 19 Liebert XDP - Input and Ho
- Page 90 and 91:
Table 19 Liebert XDP - Input and Ho
- Page 92 and 93:
Table 20 Liebert XDP - Glossary (co
- Page 94 and 95:
Table 20 Liebert XDP - Glossary (co
- Page 96 and 97:
Table 22 Liebert XDWP (XDP-W) - Inp
- Page 98 and 99:
Table 23 Liebert DS and Liebert Pe
- Page 100 and 101:
Table 24 Liebert DS and Liebert PeX
- Page 102 and 103:
Table 24 Liebert DS and Liebert PeX
- Page 104 and 105:
Table 26 Liebert XDF - Input and Ho
- Page 106 and 107:
Modbus 485 and Modbus IP Protocols
- Page 108 and 109:
Table 29 Liebert DataMate, Liebert
- Page 110 and 111:
Modbus 485 and Modbus IP Protocols
- Page 112 and 113: Modbus 485 and Modbus IP Protocols
- Page 114 and 115: Modbus 485 and Modbus IP Protocols
- Page 116 and 117: Modbus 485 and Modbus IP Protocols
- Page 118 and 119: Modbus 485 and Modbus IP Protocols
- Page 120 and 121: Modbus 485 and Modbus IP Protocols
- Page 122 and 123: Modbus 485 and Modbus IP Protocols
- Page 124 and 125: Modbus 485 and Modbus IP Protocols
- Page 126 and 127: Modbus 485 and Modbus IP Protocols
- Page 128 and 129: Modbus 485 and Modbus IP Protocols
- Page 130 and 131: Modbus 485 and Modbus IP Protocols
- Page 132 and 133: Modbus 485 and Modbus IP Protocols
- Page 134 and 135: Modbus 485 and Modbus IP Protocols
- Page 136 and 137: Modbus 485 and Modbus IP Protocols
- Page 138 and 139: Modbus 485 and Modbus IP Protocols
- Page 140 and 141: Table 40 Liebert APM - Status and
- Page 142 and 143: Table 41 Liebert APM - Input and Ho
- Page 144 and 145: Table 42 Liebert APM - Glossary (co
- Page 146 and 147: 140 Modbus 485 and Modbus IP Protoc
- Page 148 and 149: Table 44 Liebert GXT2 and Liebert G
- Page 150 and 151: Table 47 Liebert Nfinity ® - Statu
- Page 152 and 153: Table 49 Liebert NX - Status and C
- Page 154 and 155: Table 50 Liebert NX - Input and Hol
- Page 156 and 157: Table 51 Liebert NXL SA, SR, SN, M
- Page 158 and 159: Table 52 Liebert NXL SA, SR, SN, MM
- Page 160 and 161: Table 52 Liebert NXL SA, SR, SN, MM
- Page 164 and 165: Table 52 Liebert NXL SA, SR, SN, MM
- Page 166 and 167: Table 52 Liebert NXL SA, SR, SN, MM
- Page 168 and 169: Table 52 Liebert NXL SA, SR, SN, MM
- Page 170 and 171: Table 53 Liebert NXL SA, SR, SN, M
- Page 172 and 173: 166 Modbus 485 and Modbus IP Protoc
- Page 174 and 175: 168 Modbus 485 and Modbus IP Protoc
- Page 176 and 177: Table 53 Liebert NXL SA, SR, SN, M
- Page 178 and 179: Table 53 Liebert NXL SA, SR, SN, M
- Page 180 and 181: 174 Modbus 485 and Modbus IP Protoc
- Page 182 and 183: Table 57 Liebert PowerSure Interact
- Page 184 and 185: Table 59 Liebert Series 300 UPS - I
- Page 186 and 187: Table 61 Liebert Series 600 UPS - I
- Page 188 and 189: Table 63 Liebert Series 610 SCC UPS
- Page 190 and 191: 184 Modbus 485 and Modbus IP Protoc
- Page 192 and 193: Table 65 Liebert SICE 7200 - Input
- Page 194 and 195: Table 66 Liebert NPower - Input an
- Page 196 and 197: Table 67 Liebert BDSU - Status and
- Page 198 and 199: Table 68 Liebert BDSU - Input and H
- Page 200 and 201: 4.0 BACNET COMMUNICATIONS BACnet Co
- Page 202 and 203: 4.1.3 Standard Object Types Support
- Page 204 and 205: BACnet Communications - BACnet Prot
- Page 206 and 207: 4.2 Precision Cooling Products 200
- Page 208 and 209: 202 BACnet Communications - Precisi
- Page 210 and 211: 204 BACnet Communications - Precisi
- Page 212 and 213:
206 BACnet Communications - Precisi
- Page 214 and 215:
208 BACnet Communications - Precisi
- Page 216 and 217:
210 BACnet Communications - Precisi
- Page 218 and 219:
212 BACnet Communications - Precisi
- Page 220 and 221:
214 BACnet Communications - Precisi
- Page 222 and 223:
Ext Standby Glycol Pump On - Event
- Page 224 and 225:
218 BACnet Communications - Precisi
- Page 226 and 227:
220 BACnet Communications - Precisi
- Page 228 and 229:
Table 73 Liebert CRV - Binary Data
- Page 230 and 231:
Table 74 Liebert CRV - Analog Data
- Page 232 and 233:
Table 74 Liebert CRV - Analog Data
- Page 234 and 235:
Table 75 Liebert CRV - Multistate D
- Page 236 and 237:
Table 76 Liebert CRV - Glossary (co
- Page 238 and 239:
Table 76 Liebert CRV - Glossary (co
- Page 240 and 241:
Table 76 Liebert CRV - Glossary (co
- Page 242 and 243:
Table 77 Liebert HPC - Binary Data
- Page 244 and 245:
Table 77 Liebert HPC - Binary Data
- Page 246 and 247:
Table 78 Liebert HPC - Analog Data
- Page 248 and 249:
Table 79 Liebert HPC - Multistate D
- Page 250 and 251:
Table 80 Liebert HPC - Glossary (co
- Page 252 and 253:
246 BACnet Communications - Precisi
- Page 254 and 255:
248 BACnet Communications - Precisi
- Page 256 and 257:
Table 82 Liebert XDP, Liebert XDWP
- Page 258 and 259:
Table 83 Liebert XDP, Liebert XDWP
- Page 260 and 261:
Table 83 Liebert XDP, Liebert XDWP
- Page 262 and 263:
Table 83 Liebert XDP, Liebert XDWP
- Page 264 and 265:
Table 84 Liebert XDP, Liebert XDWP
- Page 266 and 267:
Table 84 Liebert XDP, Liebert XDWP
- Page 268 and 269:
Table 84 Liebert XDP, Liebert XDWP
- Page 270 and 271:
Table 84 Liebert XDP, Liebert XDWP
- Page 272 and 273:
Table 86 Liebert Mini-Mate2 8 Ton -
- Page 274 and 275:
Table 87 Liebert APM - Binary Data
- Page 276 and 277:
Table 88 Liebert APM - Analog Data
- Page 278 and 279:
Table 90 Liebert APM - Glossary Dat
- Page 280: