Table 83 Liebert XDP, Liebert XDWP (XDP-W) - Multistate Data (continued)<br />

257<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

System Control Mode Multistate_Value 839 4707_1 RD<br />

1 = Internal (Auto)<br />

2 = External<br />

(Manual)<br />

System Operating State Reason Multistate_Value 840 5074_1 RD<br />

1 = Reason<br />

Unknown<br />

2 = Network<br />

Display<br />

3 = Alarm<br />

4 = Schedule<br />

5 = Remote System<br />

6 = External Input<br />

7 = Local Display<br />

System On/Off Control<br />

System Event Configuration<br />

Multistate_Value 841 5143_1 RW 1 = Off / 2 = On<br />

Customer Input 1 - Event Control Multistate_Value 852 4718_1 RW<br />

Customer Input 1 - Event Type Multistate_Value 853 4719_1 RW<br />

System Condensation Detected - Event Control Multistate_Value 854 4712_1 RD<br />

System Condensation Detected - Event Type Multistate_Value 855 4713_1 RW<br />

Shutdown - Loss Of Power - Event Control Multistate_Value 856 4715_1 RD<br />

Shutdown - Loss Of Power - Event Type Multistate_Value 857 4716_1 RW<br />

Smoke Detected - Event Control Multistate_Value 858 4721_1 RW<br />

Smoke Detected - Event Type Multistate_Value 859 4722_1 RW<br />

Water Under Floor - Event Control Multistate_Value 860 4724_1 RW<br />

Water Under Floor - Event Type Multistate_Value 861 4725_1 RW<br />

Service Required - Event Control Multistate_Value 862 4727_1 RW<br />

Service Required - Event Type Multistate_Value 863 4728_1 RW<br />

Fan Issue - Event Control Multistate_Value 864 4730_1 RW<br />

Fan Issue - Event Type Multistate_Value 865 4731_1 RW<br />

System Events<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

System Event Acknowledge/Reset Multistate_Value 876 4717_1 WO<br />

Object<br />

Name Access Notes<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Disabled<br />

2 = Enabled<br />

1 = Message<br />

2 = Warning<br />

3 = Alarm<br />

1 = Reset<br />

2 = Acknowledge