Table 78 Liebert HPC - Analog Data<br />

Controller Liebert iCOM v4<br />

239<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Object<br />

Extra<br />

Data Description<br />

Compressors<br />

Object Type Instance Name Access Notes Notes<br />

Compressor Shut Down - Ambient Air Low<br />

Temp Limit<br />

Analog_Value 1 5262_1 RW Units: deg C 1, 2<br />

Compressor Shut Down - Ambient Air Low<br />

Temp Limit<br />

Compressors - Compressor 1<br />

Analog_Value 10001 5262_1_deg_F RW Units: deg F 1, 2<br />

Compressor Head Pressure Analog_Value 12 5266_1_1 RD Units: bar 1, 2<br />

Compressor Hours Analog_Value 13 5267_1_1 RW Units: hr 1, 2<br />

Compressor Hours Threshold<br />

Compressors - Compressor 2<br />

Analog_Value 14 5268_1_1 RW Units: hr 1, 2<br />

Compressor Head Pressure Analog_Value 25 5266_1_2 RD Units: bar 1, 2<br />

Compressor Hours Analog_Value 26 5267_1_2 RW Units: hr 1, 2<br />

Compressor Hours Threshold<br />

Compressors - Compressor 3<br />

Analog_Value 27 5268_1_2 RW Units: hr 1, 2<br />

Compressor Head Pressure Analog_Value 195 5266_1_3 RD Units: bar 2<br />

Compressor Hours Analog_Value 196 5267_1_3 RW Units: hr 2<br />

Compressor Hours Threshold<br />

Compressors - Compressor 4<br />

Analog_Value 197 5268_1_3 RW Units: hr 2<br />

Compressor Head Pressure Analog_Value 215 5266_1_4 RD Units: bar 2<br />

Compressor Hours Analog_Value 216 5267_1_4 RW Units: hr 2<br />

Compressor Hours Threshold<br />

Condensers 1<br />

Analog_Value 217 5268_1_4 RW Units: hr 2<br />

Condenser Fan Speed<br />

Condensers 2<br />

Analog_Value 38 5276_1 RD Units: % 1, 2<br />

Condenser Fan Speed<br />

Condenser 3<br />

Analog_Value 49 5276_2 RD Units: % 1, 2<br />

Condenser Fan Speed<br />

Condenser 4<br />

Analog_Value 52 5276_3 RD Units: % 2<br />

Condenser Fan Speed<br />

Fluid<br />

Analog_Value 55 5276_4 RD Units: % 2<br />

Fluid Pressure Analog_Value 60 5279_1 RD Units: bar 1, 2<br />

Fluid Cooling Proportional B<strong>and</strong> Analog_Value 61 5281_1 RW Units: deg C 1, 2<br />

Fluid Cooling Proportional B<strong>and</strong><br />

Fluid - Supply (Outlet) Fluid<br />

Analog_Value 10061 5281_1_deg_F RW Units: deg F 1, 2<br />

Supply Fluid Temp Set Point 1 Analog_Value 72 5283_1_1 RW Units: deg C 1, 2<br />

Supply Fluid Temp Set Point 1 Analog_Value 10072 5283_1_1_deg_F RW Units: deg F 1, 2<br />

Supply Fluid Temp Set Point 2 Analog_Value 73 5284_1_1 RW Units: deg C 1, 2<br />

Supply Fluid Temp Set Point 2 Analog_Value 10073 5284_1_1_deg_F RW Units: deg F 1, 2<br />

Supply Fluid Over Temp Alarm Threshold Analog_Value 74 5285_1_1 RW Units: deg C 1, 2<br />

Supply Fluid Over Temp Alarm Threshold Analog_Value 10074 5285_1_1_deg_F RW Units: deg F 1, 2<br />

Supply Fluid Over Temp Warning Threshold Analog_Value 75 4644_1_1 RW Units: deg C 1, 2<br />

Supply Fluid Over Temp Warning Threshold Analog_Value 10075 4644_1_1_deg_F RW Units: deg F 1, 2