Table 13 Liebert HPC (Chiller) - Input <strong>and</strong> Holding<br />

Data Label<br />

Controller Liebert iCOM v4<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input<br />

Register<br />

Holding<br />

Register<br />

Server Class 30385 1<br />

Compressors<br />

Compressor Shut Down - Ambient Air Low Temp<br />

Limit<br />

Compressor Shut Down - Ambient Air Low Temp<br />

Limit<br />

Compressor 1<br />

Compressor State 30394 1<br />

46<br />

# of<br />

Reg Scale Notes/Units<br />

1 = UPS<br />

2 = AIR<br />

3 = PMP<br />

4 = PDU<br />

Extra<br />

Notes<br />

1, 2<br />

30389 40389 1 Units : deg C 1, 2<br />

30390 40390 1 Units : deg F 1, 2<br />

0 = off<br />

1 = on<br />

Compressor Capacity Control State 30395 1<br />

0 = off<br />

1 = on<br />

1, 2<br />

Compressor Head Pressure 30396 1 Scale : x / 10 Units : bar 1, 2<br />

Compressor Hours 30397 40397 1 Units : hr 1, 2<br />

Compressor Hours Threshold<br />

Compressor 2<br />

30398 40398 1 Units : hr 1, 2<br />

Compressor State 30402 1<br />

0 = off<br />

1 = on<br />

Compressor Capacity Control State 30403 1<br />

0 = off<br />

1 = on<br />

1, 2<br />

Compressor Head Pressure 30404 1 Scale : x / 10 Units : bar 1, 2<br />

Compressor Hours 30405 40405 1 Units : hr 1, 2<br />

Compressor Hours Threshold<br />

Compressor 3<br />

30406 40406 1 Units : hr 1, 2<br />

Compressor State 30530 1<br />

0 = off<br />

1 = on<br />

Compressor Capacity Control State 30531 1<br />

0 = off<br />

1 = on<br />

2<br />

Compressor Head Pressure 30532 1 Scale : x / 10 Units : bar 2<br />

Compressor Hours 30533 40533 1 Units : hr 2<br />

Compressor Hours Threshold<br />

Compressor 4<br />

30534 40534 1 Units : hr 2<br />

Compressor State 30550 1<br />

0 = off<br />

1 = on<br />

Compressor Capacity Control State 30551 1<br />

0 = off<br />

1 = on<br />

2<br />

Compressor Head Pressure 30552 1 Scale : x / 10 Units : bar 2<br />

Compressor Hours 30553 40553 1 Units : hr 2<br />

Compressor Hours Threshold<br />

Condensers 1<br />

30554 40554 1 Units : hr 2<br />

Condenser Fan Speed<br />

Condensers 2<br />

30410 1 Units : % 1, 2<br />

Condenser Fan Speed 30414 1 Units : % 1, 2<br />

1, 2<br />

1, 2<br />

2<br />

2