Table 68 Liebert BDSU - Input <strong>and</strong> Holding (continued)<br />

Data Description<br />

Float Current<br />

String 1 - 32<br />

Ripple Current<br />

String 1 - 32<br />

Total Active Alarms on a Battery String<br />

String 1 - 32<br />

Discharge State<br />

String 1 - 32<br />

Battery String Time-To-Go<br />

String 1 - 32<br />

Amp-Hours Remaining in Battery String<br />

String 1 - 32<br />

Battery String Discharge Time<br />

String 1 - 32<br />

Low Ambient Temperature Global Threshold<br />

String 1 - 32<br />

Low Ambient Temperature Global Threshold<br />

String 1 - 32<br />

High Ambient Temperature Global Threshold<br />

String 1 - 32<br />

High Ambient Temperature Global Threshold<br />

String 1 - 32<br />

Battery String Overall Voltage Low Threshold<br />

String 1 - 32<br />

Battery String Overall Voltage High Threshold<br />

String 1 - 32<br />

Battery String Current High Threshold<br />

String 1 - 32<br />

Battery String Float Current Low Threshold<br />

String 1 - 32<br />

Battery String Float Current High Threshold<br />

String 1 - 32<br />

Battery String Ripple Current High Threshold<br />

String 1 - 32<br />

Cell Voltage Low Global Threshold<br />

String 1 - 32<br />

Cell Voltage High Global Threshold<br />

String 1 - 32<br />

Cell Temperature Low Global Threshold<br />

String 1 - 32<br />

Cell Temperature Low Global Threshold<br />

String 1 - 32<br />

Cell Temperature High Global Threshold<br />

String 1 - 32<br />

Cell Temperature High Global Threshold<br />

String 1 - 32<br />

Internal Resistance Low Global Threshold<br />

String 1 - 32<br />

Internal Resistance High Global Threshold<br />

String 1 - 32<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Battery Monitoring Products<br />

Input<br />

Register<br />

32114-<br />

32145<br />

32146-<br />

32177<br />

32178-<br />

32209<br />

32210-<br />

32241<br />

32242-<br />

32305<br />

32306-<br />

32337<br />

32338-<br />

32401<br />

32402-<br />

32433<br />

32434-<br />

32465<br />

32466-<br />

32497<br />

32498-<br />

32529<br />

32530-<br />

32561<br />

32562-<br />

32593<br />

32594-<br />

32625<br />

32626-<br />

32657<br />

32658-<br />

32689<br />

32690-<br />

32721<br />

32722-<br />

32753<br />

32754-<br />

32785<br />

32786-<br />

32817<br />

32818-<br />

32849<br />

32850-<br />

32881<br />

32882-<br />

32913<br />

32914-<br />

32945<br />

32946-<br />

32977<br />

191<br />

Holding<br />

Register<br />

# of<br />

Reg. Scale Notes / Units<br />

- 1 - mA DC<br />

- 1 - A AC<br />

- 1 - -<br />

- 1 -<br />

0 = Not In Progress<br />

1 = In Progress<br />

- 2 - min<br />

- 1 - AH<br />

- 2 - sec<br />

- 1 10 deg C<br />

- 1 10 deg F<br />

- 1 10 deg C<br />

- 1 10 deg F<br />

- 1 10 VDC<br />

- 1 10 VDC<br />

- 1 - A DC<br />

- 1 - mA DC<br />

- 1 - mA DC<br />

- 1 - A AC<br />

- 1 1000 VDC<br />

- 1 1000 VDC<br />

- 1 10 deg C<br />

- 1 10 deg F<br />

- 1 10 deg C<br />

- 1 10 deg F<br />

- 1 - microOhm<br />

- 1 - microOhm