<strong>BACnet</strong> Communications - Precision Cooling Products<br />
Table 74 Liebert CRV - Analog Data<br />
Controller Liebert iCOM v4<br />
Data Description<br />
Air Temperature<br />
Object Type Instance<br />
Object<br />
Name Access Notes<br />
Supply Air Temperature Analog_Value 1 5002_1 RD Units: deg C<br />
Supply Air Temperature Analog_Value 10001 5002_1 RD Units: deg F<br />
Return Air Temperature Analog_Value 2 4291_1 RD Units: deg C<br />
Return Air Temperature Analog_Value 10002 4291_1 RD Units: deg F<br />
Return Dew Point Analog_Value 3 5004_1 RD Units: deg C<br />
Return Dew Point Analog_Value 10003 5004_1 RD Units: deg F<br />
Remote Sensor Minimum Temperature Analog_Value 4 5005_1 RD Units: deg C<br />
Remote Sensor Minimum Temperature Analog_Value 10004 5005_1 RD Units: deg F<br />
Remote Sensor Maximum Temperature Analog_Value 5 5006_1 RD Units: deg C<br />
Remote Sensor Maximum Temperature Analog_Value 10005 5006_1 RD Units: deg F<br />
Remote Sensor Average Temperature Analog_Value 6 5007_1 RD Units: deg C<br />
Remote Sensor Average Temperature Analog_Value 10006 5007_1 RD Units: deg F<br />
Air Temperature Set Point Analog_Value 7 5008_1 RW Units: deg C<br />
Air Temperature Set Point Analog_Value 10007 5008_1 RW Units: deg F<br />
Cooling Proportional B<strong>and</strong> Analog_Value 8 5009_1 RW Units: deg C<br />
Cooling Proportional B<strong>and</strong> Analog_Value 10008 5009_1 RW Units: deg F<br />
Heating Proportional B<strong>and</strong> Analog_Value 9 5010_1 RW Units: deg C<br />
Heating Proportional B<strong>and</strong> Analog_Value 10009 5010_1 RW Units: deg F<br />
Air Temperature Dead B<strong>and</strong> Analog_Value 10 5011_1 RW Units: deg C<br />
Air Temperature Dead B<strong>and</strong> Analog_Value 10010 5011_1 RW Units: deg F<br />
Supply Air Over Temp Threshold Analog_Value 11 5014_1 RW Units: deg C<br />
Supply Air Over Temp Threshold Analog_Value 10011 5014_1 RW Units: deg F<br />
Supply Air Under Temp Threshold Analog_Value 12 5018_1 RW Units: deg C<br />
Supply Air Under Temp Threshold Analog_Value 10012 5018_1 RW Units: deg F<br />
Return Air Over Temp Threshold Analog_Value 13 5022_1 RW Units: deg C<br />
Return Air Over Temp Threshold<br />
Humidity<br />
Analog_Value 10013 5022_1 RW Units: deg F<br />
Supply Humidity Analog_Value 24 5027_1 RD Units: % RH<br />
Return Humidity Analog_Value 25 5028_1 RD Units: % RH<br />
Humidity Set Point Analog_Value 26 5029_1 RW Units: % RH<br />
Humidification Proportional B<strong>and</strong> Analog_Value 27 5030_1 RW Units: % RH<br />
Dehumidification Proportional B<strong>and</strong> Analog_Value 28 5031_1 RW Units: % RH<br />
Humidity Dead B<strong>and</strong> Analog_Value 29 5032_1 RW Units: % RH<br />
High Return Humidity Threshold Analog_Value 30 5033_1 RW Units: % RH<br />
Low Return Humidity Threshold<br />
Fans<br />
Analog_Value 31 5035_1 RW Units: % RH<br />
Fan Speed Proportional B<strong>and</strong> Analog_Value 42 5048_1 RW Units: deg C<br />
Fan Speed Proportional B<strong>and</strong> Analog_Value 10042 5048_1 RW Units: deg F<br />
Fan Speed Manual Set Point Analog_Value 43 5049_1 RW Units: %<br />
Fan Speed Maximum Set Point Analog_Value 44 5050_1 RW Units: %<br />
Fan Speed Minimum Set Point Analog_Value 45 5051_1 RW Units: %