Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input Holding<br />

Data Label<br />

Register Register # of Reg Scale Notes/Units<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 6 Temperature Sensor 1<br />

31173 41173 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31179 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 6 Temperature Sensor 2<br />

31180 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31186 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 6 Temperature Sensor 4<br />

31187 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31200 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 6 Secondary Fans<br />

31201 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31207 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 7 Temperature Sensor 1<br />

31208 41208 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31214 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 7 Temperature Sensor 2<br />

31215 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31221 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 7 Temperature Sensor 4<br />

31222 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31235 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 7 Secondary Fans<br />

31236 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31242 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 8 Temperature Sensor 1<br />

31243 41243 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31249 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 8 Temperature Sensor 2<br />

31250 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31256 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 8 Temperature Sensor 4<br />

31257 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31270 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature 31271 1 Scale : x / 10 Units : deg F<br />