Table 12 Liebert HPC (Chiller) - Status <strong>and</strong> Coil (continued)<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Controller Liebert iCOM v4<br />

Data Label Status Coil<br />

Compressor Capacity Normal 10238 1 Active on Alarm 2<br />

Compressor Contactor Issue<br />

Condensers 1<br />

10239 1 Active on Alarm 2<br />

Condenser Fan Issue 10046 1 Active on Alarm 1, 2<br />

Low Condenser Refrigerant Pressure 10047 1 Active on Alarm 1, 2<br />

Condenser Max Fan Speed Override<br />

Condensers 2<br />

10048 1 Active on Alarm 1, 2<br />

Condenser Fan Issue 10058 1 Active on Alarm 1, 2<br />

Low Condenser Refrigerant Pressure 10059 1 Active on Alarm 1, 2<br />

Condenser Max Fan Speed Override<br />

Condensers 3<br />

10060 1 Active on Alarm 1, 2<br />

Condenser Fan Issue 10062 1 Active on Alarm 2<br />

Low Condenser Refrigerant Pressure 10063 1 Active on Alarm 2<br />

Condenser Max Fan Speed Override<br />

Condensers 4<br />

10064 1 Active on Alarm 2<br />

Condenser Fan Issue 10066 1 Active on Alarm 2<br />

Low Condenser Refrigerant Pressure 10067 1 Active on Alarm 2<br />

Condenser Max Fan Speed Override<br />

Fluid<br />

10068 1 Active on Alarm 2<br />

Low Fluid Pressure<br />

Supply (Outlet) Fluid<br />

10070 1 Active on Alarm 1, 2<br />

Supply Fluid Over Temp 10081 1 Active on Alarm 1, 2<br />

Supply Fluid Under Temp 10082 1 Active on Alarm 1, 2<br />

Supply Fluid Temp Sensor Issue<br />

Pumps<br />

10083 1 Active on Alarm 1, 2<br />

All Pumps Loss of Flow 10107 1 Active on Alarm 1, 2<br />

Pump 1 Loss of Flow 10108 1 Active on Alarm 1, 2<br />

Pump 2 Loss of Flow<br />

Pump 1<br />

10109 1 Active on Alarm 1, 2<br />

Pump Hours Exceeded<br />

Pump 2<br />

10120 1 Active on Alarm 1, 2<br />

Pump Hours Exceeded<br />

Free Cooling<br />

10131 1 Active on Alarm 1, 2<br />

Free Cooling Valve Hours Exceeded 10142 1 Active on Alarm 1, 2<br />

Ambient Air Temperature Sensor Issue<br />

Evaporators<br />

10143 1 Active on Alarm 1, 2<br />

Evaporator Inlet Temp Sensor Issue 10154 1 Active on Alarm 1, 2<br />

Evaporator Return Fluid Over Temp 10155 1 Active on Alarm 1, 2<br />

Evaporator Return Fluid Under Temp<br />

Evaporator 1<br />

10156 1 Active on Alarm 1, 2<br />

Evaporator Fluid Freeze - Auto Reset 10165 1 Active on Alarm 1, 2<br />

44<br />

Number<br />

of Bits Notes Extra Notes