Table 17 Liebert XDC - Glossary<br />
Data Label Data Description<br />
Auto Restart Delay<br />
Calculated Next Maintenance Month<br />
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
If power is lost, the control will delay this amount of time after power is restored<br />
before restarting the unit.<br />
Calculated month of the next scheduled maintenance. Used in conjunction with<br />
[Calculated Next Maintenance Year].<br />
Calculated Next Maintenance Year<br />
Calculated year of the next scheduled maintenance. Used in conjunction with<br />
[Calculated Next Maintenance Month].<br />
Circuit 1 Low Suction Pressure Compressor circuit 1 low suction pressure.<br />
Circuit 2 Low Suction Pressure Compressor circuit 2 low suction pressure.<br />
Cold Aisle Over Temp Threshold Upper threshold value used in the [Cold Aisle Temp Out of Range] event.<br />
Cold Aisle Temp Out of Range<br />
The air temperature in the cold aisle is either above [Cold Aisle Over Temp<br />
Threshold] or below [Cold Aisle Under Temp Threshold].<br />
Cold Aisle Under Temp Threshold Lower threshold value used in the [Cold Aisle Temp Out of Range] event.<br />
Communication Status Communication status of remote device.<br />
Compressor 1A High Head Pressure Compressor 1A high head pressure.<br />
Compressor 1A Short Cycle<br />
Compressor 1A short cycle. A short cycle is defined as turning on <strong>and</strong> off a number<br />
of times over a set time period.<br />
Compressor 1A State Compressor 1A operational state.<br />
Compressor 1B High Head Pressure Compressor 1B high head pressure.<br />
Compressor 1B Short Cycle<br />
Compressor 1B short cycle. A short cycle is defined as turning on <strong>and</strong> off a number<br />
of times over a set time period.<br />
Compressor 1B State Compressor 1B operational state.<br />
Compressor 2A High Head Pressure Compressor 2A high head pressure.<br />
Compressor 2A Short Cycle<br />
Compressor 2A short cycle. A short cycle is defined as turning on <strong>and</strong> off a number<br />
of times over a set time period.<br />
Compressor 2A State Compressor 2A operational state.<br />
Compressor 2B High Head Pressure Compressor 2B high head pressure.<br />
Compressor 2B Short Cycle<br />
Compressor 2B short cycle. A short cycle is defined as turning on <strong>and</strong> off a number<br />
of times over a set time period.<br />
Compressor 2B State Compressor 2B operational state.<br />
Cooling Capacity<br />
Cooling capacity in use, expressed as a percentage of the maximum rated<br />
capacity.<br />
Cooling Capacity Cooling capacity in use, expressed in kilowatts.<br />
Customer Input 1 Customer input 1.<br />
Dew Point Temperature Dew point temperature, using the highest reading from all sensors.<br />
Ext Air Over Temp Threshold<br />
Threshold value used in the ([Ext Air Sensor A Over Temperature], [Ext Air<br />
Sensor B Over Temperature]...) events.<br />
Ext Air Sensor A Dew Point Temp Dew point temperature as measured by external air sensor A.<br />
Ext Air Sensor A Humidity Relative humidity as measured by external air sensor A.<br />
Ext Air Sensor A Issue The external air sensor A is disconnected or the signal is out of range.<br />
Ext Air Sensor A Over Temperature [Ext Air Sensor A Temperature] has exceeded [Ext Air Over Temp Threshold].<br />
Ext Air Sensor A Temperature Air temperature as measured by external air sensor A.<br />
Ext Air Sensor A Under Temperature<br />
[Ext Air Sensor A Temperature] has dropped below [Ext Air Under Temp<br />
Threshold].<br />
Ext Air Sensor B Dew Point Temp Dew point temperature as measured by external air sensor B.<br />
Ext Air Sensor B Humidity Relative humidity as measured by external air sensor B.<br />
Ext Air Sensor B Issue The external air sensor B is disconnected or the signal is out of range.<br />
Ext Air Sensor B Over Temperature [Ext Air Sensor B Temperature] has exceeded [Ext Air Over Temp Threshold].<br />