<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 27 Liebert Challenger 3000 , Liebert Deluxe System/3 , Liebert Himod , Liebert ICS <br />

- Input <strong>and</strong> Holding - LAM (continued)<br />

Controller Advanced Microprocessor - LAM<br />

Liebert Products<br />

Data Description<br />

Liebert Challenger 3000<br />

Liebert Deluxe System/3<br />

Liebert Himod (LNA version - Using Liebert Sitescan ® )<br />

Liebert ICS<br />

Available Points<br />

Input<br />

Register<br />

Holding<br />

Register<br />

# of<br />

Reg. Scale Notes / Units<br />

Inverter on Bypass - 40291 1 - Bit 3<br />

St<strong>and</strong>by Fan On - 40291 1 - Bit 4<br />

Loss of Emergency Power - 40291 1 - Bit 5<br />

Local Alarm 1 - 40291 1 - Bit 6<br />

Local Alarm 2 - 40291 1 - Bit 7<br />

Off by Remote Shutdown - 40291 1 - Bit 8<br />

Local Alarm 3 - 40291 1 - Bit 9<br />

Local Alarm 4 - 40291 1 - Bit 10<br />

Compressor 1 Run Hours - 40019 1 - -<br />

Compressor 2 Run Hours - 40020 1 - -<br />

Fan Motor Run Hours - 40021 1 - -<br />

Humidifier Run Hours<br />

Setpoints (View)<br />

- 40022 1 - -<br />

Temperature Setpoint - 40010 1 - (R/W)<br />

Temperature Tolerance - 40011 1 - (R/W)<br />

Humidity Setpoint - 40012 1 - (R/W)<br />

Humidity Tolerance - 40013 1 - (R/W)<br />

High Temp Alarm Setpoint - 40014 1 - (R/W)<br />

Low Temp Alarm Setpoint - 40015 1 - (R/W)<br />

High Humd Alarm Setpoint - 40016 1 - (R/W)<br />

Low Humidity Alarm Setpoint - 40017 1 - (R/W)<br />

Winter Start Delay - 40028 1 - Minutes (R/W)<br />

Auto Flush Rate - 40029 1 - % (R/W)<br />

Chill Water Flush Rate - 40030 1 - Hours (R/W)<br />

Auto Restart Delay<br />

Control Points (Set)<br />

- 40031 1 - 0.1 minute (R/W)<br />

Unit On / Off - 40349 1 - Bit 0 On=unit Off; Bit 1 On=unit On<br />

Temperature Setpoint - 40350 1 - -<br />

Temperature Tolerance - 40350 1 1000 -<br />

Humidity Setpoint - 40351 1 - -<br />

Humidity Tolerance - 40351 1 1000 -<br />

Reheat Lockout - 40349 1 - Bit 2 On=RH Off; Bit 3 On=RH On<br />

Humidifier Lockout<br />

Trendable Points (Set)<br />

- 40349 1 - Bit 4 On=HL Off; Bit 5 On=HL On<br />

Temperature - - 1 - -<br />

Humidity<br />

Reports<br />

- - 1 - -<br />

Trend - - 1 - -<br />

Status - - 1 - -<br />

If the Scale column has a value for a Data Description, multiply the <strong>Modbus</strong> value by the value in the Scale column.<br />

100