<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Table 30 Liebert Mini-Mate2 8 Ton - Input <strong>and</strong> Holding - L8T<br />

Controller L8T<br />

Liebert Products Liebert Mini-Mate2 8 Ton<br />

Available Points<br />

Input Holding # of<br />

Data Description<br />

Status Points (View)<br />

Register Register Reg. Scale Notes / Units<br />

Temperature - 40001 1 - -<br />

Humidity - 40002 1 - -<br />

Cooling - 40003 1 - 1=On / 0=Off<br />

Heating - 40004 1 - 1=On / 0=Off<br />

Humidification - 40005 1 - 1=On / 0=Off<br />

De-humidification - 40006 1 - 1=On / 0=Off<br />

Econ-O-Cycle - 40007 1 - 1=On / 0=Off<br />

Stages - 40008 1 - -<br />

% Capacity - 40009 1 - -<br />

Analog input 1 - 40023 1 -<br />

A/D raw value w/ slope =1<br />

<strong>and</strong> offset = 0<br />

Analog input 2 - 40024 1 -<br />

A/D raw value w/ slope =1<br />

<strong>and</strong> offset = 0<br />

Analog input 3 - 40025 1 -<br />

A/D raw value w/ slope =1<br />

<strong>and</strong> offset = 0<br />

Analog input 4<br />

Alarm Points<br />

- 40026 1 -<br />

A/D raw value w/ slope =1<br />

<strong>and</strong> offset = 0<br />

Communications - 40289 1 - Bit 0<br />

Local Off - 40289 1 - Bit 1<br />

Remote Off - 40289 1 - Bit 2<br />

High Head Pressure 1 - 40289 1 - Bit 3<br />

High Head Pressure 2 - 40289 1 - Bit 4<br />

Loss of Airflow - 40289 1 - Bit 5<br />

St<strong>and</strong>by Glycol Unit On - 40289 1 - Bit 6<br />

Not Used - 40289 1 - Bit 7<br />

Change Filters - 40289 1 - Bit 8<br />

High Temperature - 40289 1 - Bit 9<br />

Low Temperature - 40289 1 - Bit 10<br />

High Humidity - 40290 1 - Bit 0<br />

Low Humidity - 40290 1 - Bit 1<br />

Humidifier Problem - 40290 1 - Bit 2<br />

Smoke Detected - 40290 1 - Bit 8<br />

Loss of Water - 40290 1 - Bit 9<br />

St<strong>and</strong>by Unit On - 40290 1 - Bit 10<br />

Not Used - 40291 1 - Bit 0<br />

Short Cycle - 40291 1 - Bit 1<br />

Loss of Power - 40291 1 - Bit 2<br />

Local Alarm 1 - 40291 1 - Bit 6<br />

Local Alarm 2 - 40291 1 - Bit 7<br />