Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

Fan State 31172 1<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input Holding<br />

Data Label<br />

XD System 3 Temperature Sensor 1<br />

Register Register # of Reg Scale Notes/Units<br />

Remote Sensor Temperature 31074 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 3 Temperature Sensor 2<br />

31075 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31081 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 3 Temperature Sensor 4<br />

31082 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31095 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 3 Secondary Fans<br />

31096 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31102 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 4 Temperature Sensor 1<br />

31103 41103 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31109 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 4 Temperature Sensor 2<br />

31110 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31116 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 4 Temperature Sensor 4<br />

31117 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31130 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 4 Secondary Fans<br />

31131 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31137 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 5 Temperature Sensor 1<br />

31138 41138 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31144 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 5 Temperature Sensor 2<br />

31145 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31151 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 5 Temperature Sensor 4<br />

31152 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31165 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 5 Secondary Fans<br />

31166 1 Scale : x / 10 Units : deg F<br />

77<br />

0 = off<br />

1 = on<br />

2 = economy