Table 19 Liebert XDP - Input <strong>and</strong> Holding (continued)<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Input Holding<br />

Data Label<br />

Register Register # of Reg Scale Notes/Units<br />

Remote Sensor Temperature<br />

XD System 17 Temperature Sensor 4<br />

31572 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31585 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 17 Secondary Fans<br />

31586 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31592 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 18 Temperature Sensor 1<br />

31593 41593 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31599 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 18 Temperature Sensor 2<br />

31600 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31606 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 18 Temperature Sensor 4<br />

31607 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31620 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 18 Secondary Fans<br />

31621 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31627 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 19 Temperature Sensor 1<br />

31628 41628 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31634 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 19 Temperature Sensor 2<br />

31635 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31641 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 19 Temperature Sensor 4<br />

31642 1 Scale : x / 10 Units : deg F<br />

Remote Sensor Temperature 31655 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 19 Secondary Fans<br />

31656 1 Scale : x / 10 Units : deg F<br />

0 = off<br />

Fan State 31662 1<br />

1 = on<br />

2 = economy<br />

0 = disabled<br />

Fan Economy Mode<br />

XD System 20 Temperature Sensor 1<br />

31663 41663 1<br />

1 = automatic<br />

2 = manual<br />

Remote Sensor Temperature 31669 1 Scale : x / 10 Units : deg C<br />

Remote Sensor Temperature<br />

XD System 20 Temperature Sensor 2<br />

31670 1 Scale : x / 10 Units : deg F<br />

82