Table 15 Liebert XDC - Status <strong>and</strong> Coil (continued)<br />

Controller Liebert iCOM v4<br />

Data Description Status Coil<br />

XD System 1<br />

Ext System Condensation Detected 10052 1 Active on Alarm<br />

Ext Fan Issue 10053 1 Active on Alarm<br />

Sensor Issue 10054 1 Active on Alarm<br />

Ext Remote Shutdown 10055 1 Active on Alarm<br />

Hot Aisle Temp Out of Range 10056 1 Active on Alarm<br />

Cold Aisle Temp Out of Range<br />

XD System 2<br />

10057 1 Active on Alarm<br />

Ext System Condensation Detected 10063 1 Active on Alarm<br />

Ext Fan Issue 10064 1 Active on Alarm<br />

Sensor Issue 10065 1 Active on Alarm<br />

Ext Remote Shutdown 10066 1 Active on Alarm<br />

Hot Aisle Temp Out of Range 10067 1 Active on Alarm<br />

Cold Aisle Temp Out of Range<br />

XD System 20<br />

10068 1 Active on Alarm<br />

Ext System Condensation Detected 10261 1 Active on Alarm<br />

Ext Fan Issue 10262 1 Active on Alarm<br />

Sensor Issue 10263 1 Active on Alarm<br />

Ext Remote Shutdown 10264 1 Active on Alarm<br />

Hot Aisle Temp Out of Range 10265 1 Active on Alarm<br />

Cold Aisle Temp Out of Range<br />

Messages<br />

10266 1 Active on Alarm<br />

Unit On 10282 1 Active on Alarm<br />

Unit Off 10283 1 Active on Alarm<br />

Unit St<strong>and</strong>by 10284 1 Active on Alarm<br />

Unit Partial Shutdown 10285 1 Active on Alarm<br />

Unit Shutdown 10286 1 Active on Alarm<br />

Maintenance Due 10287 1 Active on Alarm<br />

Maintenance Completed<br />

SFA Report<br />

10288 1 Active on Alarm<br />

SFA Reserved Event 1 18000 1 Active on Alarm<br />

SFA Reserved Event 2 18001 1 Active on Alarm<br />

SFA Reserved Event 3 18002 1 Active on Alarm<br />

SFA Reserved Event 4 18003 1 Active on Alarm<br />

SFA Reserved Event 5 18004 1 Active on Alarm<br />

SFA Reserved Event 6 18005 1 Active on Alarm<br />

SFA Reserved Event 7 18006 1 Active on Alarm<br />

SFA Reserved Event 8 18007 1 Active on Alarm<br />

SFA Reserved Event 9 18008 1 Active on Alarm<br />

SFA Reserved Event 10 18009 1 Active on Alarm<br />

SFA Reserved Event 11 18010 1 Active on Alarm<br />

SFA Reserved Event 12 18011 1 Active on Alarm<br />

SFA Reserved Event 13 18012 1 Active on Alarm<br />

SFA Reserved Event 14 18013 1 Active on Alarm<br />

<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />

Number<br />

of Bits Notes<br />