<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - Precision Cooling Products<br />
Table 6 Liebert Challenger 3000, Liebert Challenger ITR , Liebert CW , Liebert Deluxe System/3, Liebert<br />
DS, Liebert HPM , Liebert PeX - Status <strong>and</strong> Coil (continued)<br />
Controller Liebert iCOM v4<br />
Liebert Products<br />
Units with<br />
Liebert iCOM:<br />
Liebert HPM<br />
Chilled Water Control Valve Failure 1 10230 - 1 Active on Alarm 1, 2, 3, 4<br />
Chilled Water Control Valve Failure 2 10231 - 1 Active on Alarm 1, 2, 3, 4<br />
Unit Off 10232 - 1 Active on Alarm 1, 2, 3, 4<br />
Unit On 10233 - 1 Active on Alarm 1, 2, 3, 4<br />
Unit Partial Shutdown 10234 - 1 Active on Alarm 1, 2, 3, 4<br />
Unit Shutdown 10235 - 1 Active on Alarm 1, 2, 3, 4<br />
High Power Shutdown 10236 - 1 Active on Alarm 1, 2, 3, 4<br />
Unit St<strong>and</strong>by 10237 - 1 Active on Alarm 1, 2, 3, 4<br />
Maintenance Due 10238 - 1 Active on Alarm 1, 2, 3, 4<br />
Maintenance Completed 10239 - 1 Active on Alarm 1, 2, 3, 4<br />
Compressor Low Pressure Transducer Issue 1 10240 - 1 Active on Alarm 1, 2, 3, 4<br />
Compressor Low Pressure Transducer Issue 2 10241 - 1 Active on Alarm 1, 2, 3, 4<br />
Compressor High Pressure Transducer Issue 1 10242 - 1 Active on Alarm 1, 2, 3, 4<br />
Compressor High Pressure Transducer Issue 2 10243 - 1 Active on Alarm 1, 2, 3, 4<br />
Compressor Capacity Reduced 10244 - 1 Active on Alarm 1, 2, 3, 4<br />
Dew Point Over Temperature 10345 - 1 Active on Alarm 2, 3, 4<br />
Dew Point Under Temperature 10346 - 1 Active on Alarm 2, 3, 4<br />
Ext Dew Point Over Temperature 10347 - 1 Active on Alarm 2, 3, 4<br />
Ext Dew Point Under Temperature 10348 - 1 Active on Alarm 2, 3, 4<br />
Compressor Superheat Over Threshold 1 10349 - 1 Active on Alarm 2, 3, 4<br />
Compressor Superheat Over Threshold 2 10350 - 1 Active on Alarm 2, 3, 4<br />
Unspecified General Event 10351 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Average Over Temperature 10352 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Average Under Temperature 10353 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor System Average Over Temperature 10354 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor System Average Under Temperature 10355 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 1 10356 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 2 10357 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 3 10358 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 4 10359 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 5 10360 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 6 10361 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 7 10362 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 8 10363 - 1 Active on Alarm 2, 3, 4<br />
Remote Sensor Over Temperature 9 10364 - 1 Active on Alarm 2, 3, 4<br />
9<br />
Units with Liebert iCOM Firmware<br />
PA1.04.033.STD or later:<br />
Liebert Challenger 3000<br />
Liebert Challenger ITR<br />
Liebert CW<br />
Liebert Deluxe System/3<br />
Liebert DS<br />
Liebert PeX<br />
Available Points<br />
Data Description Status Coil # of Bits Notes Extra Notes