Table 53 Liebert NXL SA, SR, SN, MM, CD - Glossary (continued)<br />
Data Label Data Description<br />
Intelligent Parallel Minimum<br />
Redundancy<br />
Intelligent Parallel Mode<br />
Intelligent Parallel Operation<br />
State<br />
Intelligent Paralleling Shutdown<br />
Delay<br />
Internal Bypass Breaker (CB3) Internal bypass breaker (CB3)<br />
167<br />
<strong>Modbus</strong> <strong>485</strong> <strong>and</strong> <strong>Modbus</strong> <strong>IP</strong> Protocols - UPS Systems<br />
This is the minimum Number of Redundant Modules that the system will allow before<br />
bringing one or more modules back to normal operation <strong>and</strong> terminating Intelligent<br />
Paralleling.<br />
This setting gives the user the ability to choose between different energy consumption<br />
modes while Intelligent Paralleling is active <strong>and</strong> module is in st<strong>and</strong>by.<br />
This setting is used to enable or disable Intelligent Paralleling.<br />
This is the length of time the conditions for module st<strong>and</strong>by must remain satisfied<br />
before the module goes into st<strong>and</strong>by.<br />
Internal Communications Failure<br />
The control has detected a communication failure of a component on the internal<br />
communication bus<br />
Inverter Failure Inverter failure - inverter output is off<br />
Inverter Inhibit - External Restart of the inverter is inhibited by an external signal<br />
Inverter Off - External Inverter is off (operation is inhibited) due to external signal state<br />
Inverter On/Off State inverter on/off state<br />
Inverter Output Qualification<br />
Status<br />
inverter output qualification status<br />
Inverter Overload Phase A Inverter is operating with an overload on phase A<br />
Inverter Overload Phase B Inverter is operating with an overload on phase B<br />
Inverter Overload Phase C Inverter is operating with an overload on phase C<br />
Inverter Overload Time<br />
Remaining<br />
The calculated time remaining before inverter shutdown<br />
Inverter Shutdown - Overload The inverter has shutdown due to a sustained overload<br />
Inverter Static Switch SCR Short<br />
LBS Active - Master<br />
The system has detected a short across one or more inverter static switch Silicon<br />
Controlled Rectifiers (SCR)<br />
This UPS system has been selected as the functional Master Load Bus<br />
Synchronization (LBS) system.<br />
LBS Active - Slave<br />
This UPS system is synchronized to the output bus of the UPS system that has been<br />
selected as the Master Load Bus Synchronization (LBS) system.<br />
LBS Active The Load Bus Sync option is active<br />
LBS Inhibited The system has detected that conditions to perform Load Bus Sync are not satisfied<br />
Leading Power Factor The leading output Power Factor has fallen below a specified value<br />
Loss of Redundancy<br />
The multi-module collection doesn't have enough modules to redundantly support the<br />
load<br />
Main Battery Disconnect Open Main battery disconnect is open<br />
Main Controller Fault A Main Controller fault has been detected.<br />
Maintenance Bypass Breaker<br />
(MBB)<br />
Maintenance bypass breaker (MBB)<br />
Maintenance Isolation Breaker<br />
(MIB)<br />
Maintenance isolation breaker (MIB)<br />
Maximum Auto Suspensions -<br />
ECO Mode<br />
This setting sets the maximum number of automatic ECO Mode suspensions in a<br />
session.<br />
MMS Event Summary Summary of any active user alarm or fault of this module in a multi-module system<br />
MMS Inter-Module Comm Status Inter-module communication status of this module in a multi-module system<br />
MMS Loss of Sync Pulse Multi-module system loss of sync pulse<br />
MMS Low Battery Warning Multi-module system low battery warning<br />
MMS Module Alarm Active Active alarm or fault of any module in a multi-module system<br />
MMS Module Battery Current Battery current of this module in a multi-module system