20.12.2012 Views

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

Liebert® IntelliSlot® Modbus 485, Modbus IP and BACnet IP

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

205<br />

<strong>BACnet</strong> Communications - Precision Cooling Products<br />

Table 70 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Analog Data (continued)<br />

Analog Inputs 3<br />

Analog Input Reading<br />

Analog Inputs 4<br />

Analog_Value 246 5378_3 RD -<br />

Analog Input Reading<br />

System Info<br />

Analog_Value 257 5378_4 RD -<br />

BMS Timeout Period Analog_Value 268 5075_1 RW -<br />

Auto Restart Delay<br />

System Operations<br />

Analog_Value 269 4710_1 RW -<br />

Fan Speed Analog_Value 280 5077_1 RD -<br />

Compressor Utilization Analog_Value 281 5078_1 RD -<br />

Free Cooling Valve Open Position Analog_Value 282 5379_1 RD -<br />

Maintenance Ramp Analog_Value 283 4870_1 RD -<br />

Calculated Next Maintenance Month Analog_Value 284 4868_1 RD -<br />

Calculated Next Maintenance Year Analog_Value 285 4869_1 RD -<br />

Hot Water / Hot Gas Valve Open Position Analog_Value 286 5380_1 RD -<br />

Reheat Utilization Analog_Value 287 5080_1 RD -<br />

Humidifier Utilization Analog_Value 288 5081_1 RD -<br />

Dehumidifier Utilization<br />

Time<br />

Analog_Value 289 5079_1 RD -<br />

System Date <strong>and</strong> Time Analog_Value 300 4293_1 RW -<br />

Table 71 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3, Liebert<br />

DS, Liebert HPM, Liebert PeX - Multistate Data<br />

Protocol<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Server Class Multistate_Value 1 4553_1 RD<br />

Air<br />

Air Temperature Control Type Multistate_Value 12 5324_1 RW<br />

Air - Supply Air<br />

Supply Air Temperature Sensor Control Multistate_Value 23 5332_1_1 RW<br />

Humidity<br />

Controller Liebert iCOM v4<br />

Data Description Object Type Instance<br />

Humidity Proportional Control Type Multistate_Value 34 5340_1 RW<br />

Object<br />

Name Access Notes<br />

Object<br />

Name Access Notes<br />

1 = UPS<br />

2 = AIR<br />

3 = PMP<br />

4 = PDU<br />

1 = Proportional<br />

2 = Prop+Integral<br />

3 = Intelligent<br />

1 = Disabled<br />

2 = Limit<br />

3 = Control<br />

4 = Temp Only<br />

1 = Relative<br />

2 = Compensated<br />

3 = Predictive